EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 19 -
Reverse connected current inputs correction set-up
1
use
and
buttons to
select page “SET sys cont”
2-1
Press to
enter Phase A , the
default is Frd (forward)
2-2
use
and
buttons to
Phase B or C setting pages
How to operate if phase A is reversely connected
1
Go to phase A setting page
2
Press
to enter the selection
routine. The Frd will flash.
Use
button to change Frd to Rev.
Press
to confirm the setting and press
to return to the main set up menu.