30379
190
L2 total kvarh (3)
kvarh
01
7a
√
√
√
30381
191
L3 total kvarh (3)
kvarh
01
7c
√
√
√
Notes:
1. The power factor has its sign adjusted to indicate the direction of the current. Positive refers
to forward current, negative refers to reverse current.
2. The power sum demand calculation is for import
– export.
3. Total kWh / kVarh equals to export.
1.3 Modbus Protocol Holding Registers and Digital meter set up
Holding registers are used to store and display instrument configuration settings. All holding
registers not listed in the table below should be considered as reserved for manufacturer use
and no attempt should be made to modify their values.
The holding register parameters may be viewed or changed using the Modbus Protocol. Each
parameter is held in two consecutive 4X registers. Modbus Protocol Function Code 03 is used
to read the parameter and Function Code 16 is used to write. Write to only one parameter per
message.
1.3.1 SDM630Modbus MODBUS Protocol Holding Register Parameters
Address
Register
Parameter
Number
Paramet-
er
Modbus
Protocol
Start
Address
Hex
Valid range
Mode
High
Byte
Low
Byte
40003
2
Demand
Period
00
02
Write demand period: 0, 5,8, 10,
15, 20, 30 or 60 minutes, default
60. Setting the period to 0 will
cause the demand to show the
current parameter value, and
demand max to show the
maximum parameter value since
last demand reset.
Length : 4 byte
Data Format : Float
r/w
40011
6
System
Type
00
0A
Write system type: 3p4w = 3, 3p3w
= 2 & 1p2w= 1
Requires password, see parameter
13
Length : 4 byte
r/wp
B+G e-tech GmbH °
DE 01979 Lauchhammer °
www.eastron-germany.de