8
EASTRON SDM530C User Manual
06-2018 V1.0
2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn
2
Keep pressing
for 3 second, the current
selection will flash, use
and
to
change the Modbus address. Options: 1~247
Keep press
for 3s to confirm the
selection.
3
Keep pressing
for 3 second, the current
selection will flash, use
and
to
change the Baud rate. Options: 1200,
2400,4800,9600 ( default )
Keep press
for 3s to confirm the
selection.
4
Keep pressing for 3 second, the current selection
will flash, use
and
to change the
Parity. Options: EVEN,ODD,NONE ( default )
Keep press
for 3s to confirm the
selection.
Keep pressing
for 3 second, the current
selection will flash, use
and
to
choose Pulse Constant. Options: 1000, 100, 10, 1
Example shows pulse constant 1000imp/kWh.
Please note: The LED rate for pulse is fixed with
1000imp/kWh.
5
Keep pressing
for 3 second, the pulse will
flash, use
and
to choose Pulse
Duration. Options: 60, 100, 200ms