9
EASTRON SDM530C User Manual
06-2018 V1.0
2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn
Example shows the Pulse Duration is 100ms.
Please note: When the Pulse Constant is
1000imp/kWh, the pulse duration is fixed with
35ms.
6
This option allows user to configure the pulse
output. The output ca be set to provide a pulse
for a defined amount of active or reactive
energy. Use this section to set up the relay pulse
output-Units: kWh, kVArh.
Default: P kWh ( active energy)
Example shows Pulse Output type: kWh ( active )
Example shows Pulse Output type: kVArh
(reactive)
This sets the period in minutes over which the
current and power reading are integrated for
maximum demand measurement. The options
are 0~60.
Example shows the DIT is 60 minutes.
This sets the Display scroll time.
Options:0~30s
Example shows the display will scroll every 30s.
Please note: 0 means the display scroll is closed.
No display scroll
This meter provides a function to set the blue
backlight lasting time (off on, 5, 10, 20, 30, 60,
120mins )
Example shows the backlight will be off in
60mins.
Please note: Off means backlight always off; On
means the backlight always on here.