05) Damping:
From the main screen, press the
MENU key then the number 02.
Enter the password (default is
00000000) and press the ENTER key
followed by 05).
Five damping options, from none
to 120 seconds are available.
Damping will smooth the
displayed values when
encountering a fluctuating signal.
Press MENU and ENTER to store
changes.
06) Lost Signal Time:
Press MENU, 02, Password,
ENTER and 06.
The response to lost signals can be delayed from 5 seconds to
16 minutes by selecting a setting from 01) to 08).
The selection will automatically change to “Lost Signal Action”
after choosing a lost signal time.
Lost signal action:
Some applications require special
handling of lost signals. It can be
important to indicate or ignore such
occurrences. The Accuron 7200 offers
three lost signal management options:
01) Fail to Zero
02) Fail to Span
03) Hold last Value.
Press MENU and ENTER to store
changes.
58
59
INSTALLATION & OPERATING MANUAL
ACCURON CARTRIDGE METER
SERIES 7200
Application Full Scale:
Enter the Full Scale values for level,
velocity and flow.
Press ENTER to advance to
SHUTDOWN screen.
Application Flow Rate
Shutdown:
It may be desirable to force
the meter not to register
insignificant flow. The
APPLICATION SHUTDOWN
allows the user to enter a
minimum registered flow
rate.
Press the MENU key and
ENTER to store changes.