Preparation
Install the components in the distribution
box according to the wiring diagram at the
end of this document.
Attach the 3 Rogowski Coils or CT Clamps
around the incoming phase cables. The
coils must be installed in the right direction
as per the following arrow →. If the coils are
installed in the wrong direction negative
values might appear on the metre reader.
Configure Eastron 3-phase meter reader:
– Press and hold the "E"-button for 3
seconds
– The metre reader asks for a password.
The password is always "1000" (Press
"Arrow up↑" one time to change)
– Press and hold the "E"-button for 3
seconds (Display shows "Set - Addr -
001")
Connection
Main distribution unit or secondary
distribution unit / facade metre reader unit.
Rogowski Coils must be fitted in the correct
order to read incoming power line.
Accessibility to WiFi to facilitate latest
software updates for the Equalizer.
Fuse 3-pool 10A (not included).
Installation
1.
2.
3.
1.
2.
3.
– Press "Arrow down↓" 5 times (Display
shows "Set - Ct1 - 0,5 kA")
– Press and hold "E"- button for 3 seconds
to select
– Set the Rogowski Coils amperes (500A)
or CT Clamps amperes (100A). Use
arrows →←↑↓ to select which figure you
want to change. (The display will now
show "Set - CT1 - 0,5 kA" when using coils
or “Set - CT1 - 0100” when using CT’s)
– Press and hold the "E"-button for 3
seconds to confirm (Display will show
"Good" to confirm the setting)
– Press "U/I"-button to return to the main
menu and "Arrow down↓"
– Now you are done and able to see the
phase reading on the display
Tips! Prepare installation in a new
encapsulation (not included):
– 4 Modules for Eastron 3-phase meter
reader
– 3 Modules for Tufvasson’s electricity
transformer
– 3 Modules for fuse 10A 3-pool (Eastron
3-phase meter reader)
– 3 Modules for fuse of charge box