6. ELECTRICAL WIRING
12
CAUTION
CAUTION
Fig.5-14
Fig.5-13
Fig.6-2
3. Please use attached heat-insulating materials do the heat
insulation without clearance for the connecting parts of the
indoor unit pipes.
Cut from upward
Site pipe side
Affiliated heat pump belt
The unit body
Φ9.5
Φ12.7
Φ15.9
0.057kg
0.110kg
0.170kg
Φ6.4
0.022kg
Table 5-13
5.12 Refrigerant Amount to be Added
Calculate the added refrigerant according to the diameter and
the length of the liquid side pipe of the outdoor unit/indoor unit
connection. Calculate the refrigerant adding amount, adding
refrigerant R410A.
Liquid Side Piping
Diameter
Refrigerant to be Added
Permeter Piping
NOTE: R410A refrigerant should be added in liquid quantifiedly by
electronic scale.
5-13 Manifold installation key points
Install it in a horizonal level, error angle should less than 10°.
It may result in damage if installing in a wrong way
Please select power source for indoor unit and outdoor unit
respectively.
The power supply has specified branch circuit with leakage
protector and manual switch.
The outdoor unit model which corresponding to different outdoor
unit power supply should refer to the nameplate.(Please set all
the indoor unit power of one system into the same branch circuit.)
Please put the connective wire system between indoor unit and
outdoor unit with the refrigerant system together.
Use 3-core shielded wire as indoor unit and outdoor unit signal
wire.
The installation should comply with local electric standard.
Power wiring should be engaged by specialized electrician.
A
B
N
C
380-415V 3N
~
50Hz
XT2
Fig.6-1
K1 K
2
E O A E
X Y E P Q E
6.1 Outdoor unit wiring terminal instructions
Outdoor unit
central monitor
Indoor unit
central monitor
Indoor unit
central monitor
Digital
electric meter
NOTE:Use 3-core shielded wire to ground wiring
NOTE: Outdoor unit central monitor, digital electric meter, indoor unit
central monitor are all optional components in the dotted box,
if necessary, please contact to the local dealer to buy those.
380-415V
3N~ 50Hz
6mm
2
40
40 Under 100mA
0.1 sec
4×10mm
2
4×6mm
2
45
kW
33.5
kW
40kW
380-415V
3N~ 50Hz
10mm
2
50
50 Under 100mA
0.1 sec
4×16mm
2
4×10mm
2
Table 6-1
Item
Model
Power
Source
6.2 Indoor unit system wiring
1. Individual power supply (without power supply device)
(See the table below)
Thinnest electric wire diameter(mm
2
)
(Metal tube synthetic resin wiring)
Under
20m
Under
50m
Ground
wire
Breaker Fuse
Hand switch
Leakage
protector
Wiring diameters and continuous lengths in the table are the
situation that voltage decrease degree is within 2%, when the
wiring continuous length exceeds the values in the table, choose
the wire diameter according to regulations
V.2
Summary of Contents for EVRO-400RDC
Page 1: ...MANUAL DE INSTALACIÓN Y MANUAL DE USUARIO MODELOS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 2: ...2 ÍNDICE Manual de instalación 3 Manual de usuario 20 V 2 ...
Page 27: ...INSTALLATION S AND OWNER S MANUAL MODELS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 28: ...2 Table of contents Installation s manual 3 Owner s manual 23 V 2 ErP Information 30 ...
Page 64: ...V 2 www easelectric es ...