8
CAUTION
A
<
166
166≤A
<
230
Φ15.9
Φ9.5
Φ9.5
EVRI-BP1
EVRI-BP1
Φ19.1
230≤A
<
330
330≤A
<
460
Φ9.5
EVRI-BP2
Φ22.2
Φ12.7
EVRI-BP2
Φ25.4
460≤A
Φ12.7
EVRI-BP2
Φ25.4
Table 5-4
Table 5-5
Table 5-6
Reference table of R410A indoor unit connecting pipe
Downstream indoor
unit capacity
Main pipe dimensions
Liquid pipe
Gas pipe
Applicable
manifolds
33.5kW
40kW
Φ22.2
EVRI-BP2
EVRI-BP2
Φ25.4
45kW
Φ25.4
Φ12.7
Φ12.7
EVRI-BP2
EVRI-BP3
Φ28.6
Φ12.7
Φ12.7
Reference table of R410A outdoor unit connecting pipe
Outdoor unit
capacity
Main pipe dimensions when
equivalent length of liquid side
and gas side pipe is
<
90m
Main pipe dimensions when
equivalent length of liquid side
and gas side pipe is ≥90m
Gas side
(mm)
Liquid side
(mm)
Indoor unit
first manifold
Gas side
(mm)
Liquid side
(mm)
Indoor unit
first manifold
5.4 Diameters of outdoor unit connecting pipe
The horizontal straight pipe distance that connets to indoor unit
behind the manifold should be at least 0.5m
Use the maximum indoor and outdoor connecting pipe diameter.
CAUTION
The horizontal straight pipe distance between angle branch and
its adjacent manifold should be at least 0.5m
The horizontal straight pipe distance between 2 adjacent 2
manifold should be at least 0.5m
R410A
Joint dimension
Refrigerant
Model
Gas side
Liquid side
Pipe diameters of the indoor unit joint
Wall mounting 22~45
Wall mounting 56
Four-side air outlet 28~45
Four-side air outlet 56~80
Single-side air outlet 18~45
Single-side air outlet 56
Low static pressure 18~45
Low static pressure 56
Thin duct 71
A5 Duct 22~45
A5 Duct 56~80
A5 Duct 90~140
Φ12.7(Flare)
Φ15.9(Flare)
Φ12.7(Flare)
Φ15.9(Flare)
Φ12.7(Flare)
Φ15.9(Flare)
Φ12.7(Flare)
Φ15.9(Flare)
Φ15.9(Flare)
Φ12.7(Flare)
Φ15.9(Flare)
Φ15.9(Flare)
Φ6.4(Flare)
Φ9.5(Flare)
Φ6.4(Flare)
Φ9.5(Flare)
Φ6.4(Flare)
Φ9.5(Flare)
Φ6.4(Flare)
Φ9.5(Flare)
Φ9.5(Flare)
Φ6.4(Flare)
Φ9.5(Flare)
Φ9.5(Flare)
45kW
Φ25.4
Φ12.7
Table 5-7
Table 5-9
Table 4-8
33.5kW/40kW
Φ22.2
Pipe diameters of the outdoor unit joint
Pipe diameters of the outdoor unit joint
Gas side
Liquid side
Model
To pipe side
Φ22.2
Φ22.2
Φ25.4
Φ28.6
A
Dimensions of connecting pipe diameters in accessory
Flare(connecting to
gas side stop valve)
Accessory-
connecting pipe
Connect this end to the
connecting pipe in accessory
Accessory-connecting to elbow
Connect this end
to the main pipe
Φ22.2
Φ25.4
Φ28.6
Elbow connecting instruction
Main pipe diameters
of connecting pipes
Connecting pipe bending process
Cut the pipe at A, insert the main pipe
and weld
Cut the pipe at A, flare and weld
Insert main pipe directly and weld
22000~58000
15
45
14
40
20000~52000
40kW
14
33.5
20000~44000
33.5kW
45kW
Capacity of
Outdoor unit (kW)
Outdoor Unit
(kW)
Maximum Quantity
of Indoor unit
Sum Capacity
of Indoor unit
Capacity of indoor unit shouldn’t be greater than the sum of 130%
of outdoor unit loading.
When running with oversized bearings, attenuation will happen
correspondingly.
0.8
1.2
1.7
2
2.5
3
HP
1
22
28
36
45
56
71
80
3.2
90
3.7
100
4
112
4.5
125
5
140
Classification
of power
HP
Classification
of power
V.2
Summary of Contents for EVRO-400RDC
Page 1: ...MANUAL DE INSTALACIÓN Y MANUAL DE USUARIO MODELOS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 2: ...2 ÍNDICE Manual de instalación 3 Manual de usuario 20 V 2 ...
Page 27: ...INSTALLATION S AND OWNER S MANUAL MODELS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 28: ...2 Table of contents Installation s manual 3 Owner s manual 23 V 2 ErP Information 30 ...
Page 64: ...V 2 www easelectric es ...