6
Fig.4-8
Fig.4-7
Fig.4-6
Φ10 expansion bolt
Rubber anti-vibration
mounting
≥150mm
4.3 Outdoor unit basement
1
)
Advantages of a strong and correct basement :
①
Outdoor unit won’t subside
②
Outdoor unit won’t generate abnormal noise caused by improper
basement.
2)Basement types
①
Steel-frame basement
②
Concrete basement(See
Fig.4-6
for common practice)
225
175
555
505
1460
1360
1650
33.5kW/40kW
A
B
C
C
540
500
505
475
450
A
B
45kW
4.4 Dimension(Unit: mm)
Model
Size
Table 4-1
Fig.4-9
4.5 Pipe connection
Gas side
Liquid side
Needle valve(Pressure inspection
and refrigerant adding)
Liquid side pipe
Connecting pipe
(Accessory)
Through-pipe hole
Through-wire hole
Points of making a basement:
①
Host unit basement should be made in strong concrete ground,
See Fig 3.6 for common practice or start after field measurement
②
The basement should be completely horizontal and make sure all
the contactors can contact symmetrically.
③
Ensure the the basement supports the vertical foldings of the front
and back bottom plates directly, since its the actual bearing place.
④
Macadam base is unnecessary. But cocrete surface should be
roughed. The proportions used in mixing the concrete should be
cement 1/sand 2/ pebble 4, including Φ10reinforced rebar. Even
the surface of concrete. The edge of the basement should be
chamfered.
⑤
Drainage ditch should be arranged around the basement in order
to drainage water around the unit.
⑥
Please check endurance of the roof to ensure loading capacity
could bear the weight.
Outdoor unit
Solid ground
or roof
Concrete
foundation
V.2
Summary of Contents for EVRO-400RDC
Page 1: ...MANUAL DE INSTALACIÓN Y MANUAL DE USUARIO MODELOS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 2: ...2 ÍNDICE Manual de instalación 3 Manual de usuario 20 V 2 ...
Page 27: ...INSTALLATION S AND OWNER S MANUAL MODELS EVRO 400RDC EVRO 450RDC VRVV V 2 ...
Page 28: ...2 Table of contents Installation s manual 3 Owner s manual 23 V 2 ErP Information 30 ...
Page 64: ...V 2 www easelectric es ...