Information on grounding components:
Object
Description
1
Housing
2
M5 terminal lug with protective conductor
3
M5×13 pan head screw
PE Conductor cross-section:
4-6
mm²
4.5 Cable Specification
5. COMMISSIONING
5.1 Safety Instructions
1. Measure the frequency and voltage of grid connection and make sure
they follow the inverter’s grid connection specifications.
2. An external circuit-breaker on the AC side (or a fuse) at 1.25*AC rated
current is strongly recommended.
3. Reliability of all earth connections must be tested and valid.
4. Before commissioning, disconnect the inverter and the circuit-breaker
or fuse, and prevent accidental reconnection.
5.2 AC Wire Assembly and Connection
5.2.1
AC Commissioning
5.2.2 AC Switch Types
Please install an individual 2-stage miniature circuit breaker according
to the following specifications.
Model
Maximum output
current
(
A
)
AC Breaker Rated
current
(
A
)
Cable specifications
Nº
Item
Type
Specifications
1
PE Cable
Single-core outdoor
copper cable
Conductor cross-section:
4-6
mm
2
2
AC Output
cable
Outdoor copper
cable
Cross-section:
2.5-4
mm
2
Cable outer diameter:
5.5-12.5
mm
3
DC Input
cable
Standard outdoor PV
cable, PV1-F Model
recommended
Conductor cross-section:
2.5-6mm
2
Cable outer diameter: 4.5-7.8mm
4
Meter
/
RS485
Two-core outdoor
shielded twisted
pair cable
Conductor cross section:
0.14-1.
0
mm2
Cable outer diameter: approx
6
mm
EINSOLAR
3
V
13.8
2
0
11
10
V.
2
V.
2