EARTHSTONE OVENS PRE-ASSEMBLED GAS OVEN INSTALLATION INSTRUCTIONS
2
IMPORTAT IFORMATIO
MINIMUM CLEARANCES TO COMBUSTIBLE AND NON COMBUSTIBLE CONSTRUCTION.
COMBUSTIBLES:
SIDES 1” BACK 1”
NON COMBUSTIBLES
SIDES 0” BACK 0”
ADEQUATE CLEARACE MUST BE PROVIDED FOR AIR OPEIGS ITO THE COMBUSTIO
CHAMBER, FOR SERVICIG AD PROPER OPERATIO (PAG AD PAGW MODELS OLY). A
MIIMUM OPEIG OF 24” X 24” MUST BE LOCATED O THE BOTTOM HALF OF THE OVE. THIS
WILL ALLOW FOR PROPER COMBUSTIO AIR ITO THE BURER HOUSIG. OT HAVIG
PROPER COMBUSTIO AIR WILL CAUSE IMPROPER OPERATIO AD MAY CAUSE DAMAGE TO
THE BURER SYSTEM. ISTALLIG A SEALED ECLOSURE AROUD THE OVE SHELL MAY ALSO
CAUSE IMPROPER OPERATIO BY STARVIG THE BURER SYSTEM OF COMBUSTIO AIR. THE
USE OF RETUR AIR SYSTEMS OR OTHER VETIG SYSTEMS LOCATED WITHI SEALED
ECLOSURES WHICH SURROUD THE OVE MAY CAUSE EGATIVE PRESSURE AD I TUR
AFFECT THE OPERATIO OF THE OVE. ***SEE PAGES 14 AD 15 FOR MORE IFORMATIO
FOR MORE IFORMATIO PLEASE CALL: 800-840-4915 OR 818-553-1134
KEEP APPLIANCE FREE AND CLEAR FROM COMBUSTIBLES.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR TO THE APPLIANCE.
ELECTRICAL DIAGRAM IS LOCATED ON THE CONTROL BOX.
INSTALLATION MUST CONFORM WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE
NATIONAL FUEL GAS CODE ANSI Z223.1, THE NATURAL GAS INSTALLATION CODE CAN/CGA-B149.1 OR THE
PROPANE INSTALLATION CODE CAN/CGA-149.2, AS APPLICABLE, INCLUDING:
1
THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE MUST BE DISCONNECTED FROM THE GAS
SUPPLY PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF ½
PSI (3.45 Kpa).
2
THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS
INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM
AT THE TEST PRESSURES EQUAL TO OR LESS THAN ½ PSI (3.45 Kpa ).
THIS APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL
CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 OR THE
CANADIAN ELECTRICAL CODE, CSA C22.1, AS APPLICABLE.
ELECTRICAL AD GAS REQUIREMETS:
-1 120VAC – 2.5 AMP OUTLET
-¾ INCH GAS OUTLET
-GAS INLET PRESSURE TO OVEN: 7” W.C. FOR NATURAL, 10” W.C. FOR LP GAS
-GAS REGULATIG VALVE (I.E. MAXITROL RV 48, 3-6) AD SHUTOFF VALVE BY OTHERS
MAIFOLD GAS PRESSURE – FACTORY SETTIGS
MODEL 160-PAGW 4.5” W.C. - .190,000 BTU 130-PAGW 4.5” W.C. - 160,000 BTU
MODEL 110-PAGW 4” W.C. - 90,000 BTU
90-PAGW 4 “ W.C. - 75,000 BTU
ALL OVENS ABOVE ARE FACTORY SET AT 7” W.C. FOR LP GAS