EARTHSTONE OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS
9
COMMERCIAL DIRECT VENTING
EXISTING ROOF
EXISTING ROOF
EXISTING CEILING
EXISTING CEILING
FAN ADAPTER PLATE
FAN ADAPTER PLATE
SELKIRK METALBESTOS IPS C1 OR
METAL-FAB MODEL IPIC-1
UL LISTED GREASE DUCT/BUILDING
HEATING APPLIANCE CHIMNEY
A FIELD BUILT DUCT, CONSTRUCTED
AND INSTALLED TO THE SPECIFICATIONS
OF A GREASE DUCT PER NFPA 96 OR
THE IMC MAY ALSO BE USED.
SELKIRK METALBESTOS IPS C1 OR
METAL-FAB MODEL IPIC-1
UL LISTED GREASE DUCT/BUILDING
HEATING APPLIANCE CHIMNEY
A FIELD BUILT DUCT, CONSTRUCTED
AND INSTALLED TO THE SPECIFICATIONS
OF A GREASE DUCT PER NFPA 96 OR
THE IMC MAY ALSO BE USED.
3" MIN. CLEARANCE
3" MIN. CLEARANCE
EXHAUST FAN AND CURB POWER
VENTILATOR FOR RESTAURANT EXHAUST
APPLIANCES. RATED FOR 500F DEG.
MODELS: ENERVEX GSV SERIES. CALL
EARTHSTONE FOR DETAILS
800-840-4915 - 818-553-1134
EXHAUST FAN AND CURB POWER
VENTILATOR FOR RESTAURANT EXHAUST
APPLIANCES. RATED FOR 500F DEG.
MODELS: ENERVEX GSV SERIES. CALL
EARTHSTONE FOR DETAILS
800-840-4915 - 818-553-1134
IF A CEILING OR WALL DOES NOT
HAVE A FIRE RESISTANCE RATING
AND IS PENETRATED BY A MODEL
PS GREASE DUCT INSTALLED AT THE
CORRECT MINIMUM CLEARANCE FOR
UNENCLOSED DUCT, THEN AN
ENCLOSURE MAY NOT BE REQUIRED
AROUND THE DUCT SHAFT.
IF A CEILING OR WALL DOES NOT
HAVE A FIRE RESISTANCE RATING
AND IS PENETRATED BY A MODEL
PS GREASE DUCT INSTALLED AT THE
CORRECT MINIMUM CLEARANCE FOR
UNENCLOSED DUCT, THEN AN
ENCLOSURE MAY NOT BE REQUIRED
AROUND THE DUCT SHAFT.
3" MIN CLEARANCE TO COMBUSTIBLES
REQUIRED FOR SELKIRK
METALBESTOS
MODEL IPS C1
3" MIN CLEARANCE TO COMBUSTIBLES
REQUIRED FOR SELKIRK
METALBESTOS
MODEL IPS C1
REFER TO LOCAL JURISDICTION
AUTHORITIES.
REFER TO LOCAL JURISDICTION
AUTHORITIES.
FIGURE 18
GREASE DUCT HEATING APPLIANCE CHIMNEY ATTACHED TO PRIMARY HOOD
THIS DIAGRAM GENERALLY DEPICTS THE INSTALLATION REQUIRED TO MAINTAIN THE U.L. LISTING OF THE OVEN
FOR THIS TYPE OF VENTING APPLICATION.
FOR SPECIFIC INSTALLATION REQUIREMENTS REFER TO SELKIRK METALBESTOS MODEL IPS GREASE DUCT
INSTALLATION 8. MODEL PS AND IPS GREASE DUCT COMPLIES WITH NFPA, SBCCI, ICBO AND BOCA WHEN
PROPERLY INSTALLED PER ITS INSTALLATION INSTRUCTIONS.
CONTACT LOCAL AUTHORITY HAVING JURISDICTION REGARDING FIRE RATED DUCT SHAFT.
NOTE: OTHER U.L. LISTED SYSTEMS MAY BE SUBSTITUTED FOR THE METALBESTOS SYSTEM DEPICTED
IN THIS DIAGRAM. TO MAINTAIN THE U.L. LISTING OF THE OVEN THE SYSTEM MUST BE A U.L. LISTED
GREASE DUCT WHICH IS ALSO A U.L. LISTED BUILDING HEATING APPLIANCE CHIMNEY INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S GREASE DUCT INSTALLATION INSTRUCTIONS.
30” min.
80.000
FOR ORDERING PARTS MENTIONED ON THIS PAGE CONTACT EARTHSTONE OR YOUR
SUPPLIER. Tel: 800-840-4915- 818-553-1134
6 INCH DIAMETER GREASE DUCT - Models - 90, Café, 110, 110-Due (Dual opening)
8 INCH DIAMETER GREASE DUCT - Models 90-Due, 120, 130, 160, 110-Due (Single opening), 130-Due (Dual opening)
10 INCH DIAMETER GREASE DUCT - Model 130-Due (Single opening)
Summary of Contents for 130-DUE-PA
Page 10: ......