
25
Earthcore Industries
01/2020
Isokern Maximus Linear Series Gas Fireplace
Access Modification - Combustion Air Kits, Gas & Electrical Line Feed
4” Combustion air inlet kits are recommended by
Earthcore and may help improve fireplace operation in
homes tightly sealed and with other ventilating appliances
installed
(Figures 17 and 18)
. The following is a general
representation of a combustion air kit that is required by
Earthcore Industries.
The combustion air kit consist of a sliding stainless
steel access door affixed to a four inch (4”) in diameter
stainless steel sleeve approximately twelve inches (12”)
long. An exterior vent with dress plate, weather hood and
rodent prevention screen of a maximum one-quarter inch
(1/4”) wire mesh completes the kit.
The access door is fitted into the front 1/3 of the side
wall. The twelve inch (12”) long sleeve can be introduced
into the firebox side wall by core drilling an appropriately
sized hole at the selected firebox location. Keep the top
of the access hole no more than six inches (6”) above the
finished firebrick floor. The hole size should allow for a one-
quarter inch (1/4”) mortar joint around the air access sleeve
for heat expansion. Do not install in the rear of the firebox
because sparks will be blown into room.
The sleeve passes through the firebox side wall and
must be connected to a UL Listed Air Duct pipe that leads
to the source for outside combustion air, as directly as
possible from the fireplace. The duct cannot rise vertical
higher than the finished opening of the firebox.
We recommend not to exceed twenty feet (20’) of four
inch (4”) pipe. If you require a longer length we recommend
that you use a six inch (6”) diameter pipe for the complete
run of up to forty feet (40’).
WARNING:
Do not use combustible duct material. Avoid
installing a combustion air inlet where the opening could be
blocked by snow, bushes or other obstacles. Air inlet ducts
shall not terminate in attic, basement or garage spaces.
GAS LINE FEED
For a fireplace having the provision for installation of a gas
pipe, the provision is intended only for connection to a
decorative gas appliance.
ELECTRICAL LINE FEED
Can be routed through the LINEAR firebox side walls by
drilling an appropriately sized hole using a masonry drill
bit. Be sure to follow the gas log Appliance Manufacturer’s
explicit electrical line connection instructions for vented
masonry fireplace installations. Gas line and electric line
must be fed through separate access holes.
NOTE: Gas and electrical connections may be
brought through the rear wall of the unit and into the
area of the firebrick cavity. A gap will need to be left
in the firebrick extending from the cavity to the rear
wall of the unit for passage of the 3/8” gas line, pilot
tube, and electrical connections. Ensure all holes are
filled with mortar after installation.
Flex Duct To Fireplace
(All Parts Noncombustible)
Exterior
Wall
Exterior Air Vent
With Dress Plate
Typical Placement of
Gas or Electric Conduit
(See Detail Below)
CAUTION:
All access holes must be
grouted with mortar - after
line or conduit feed to seal
any gaps or cracks around line
feed conduits
Fire Brick Side
Gas or Electric
Conduit
NOTE: Fill Any Gaps
Around Conduit with Mortar
FIGURE 17
FIGURE18
FIGURE 19
Flex Duct To Fireplace
(All Parts Noncombustible)
Exterior
Wall
Exterior Air Vent
With Dress Plate
Typical Placement of
Gas or Electric Conduit
(See Detail Below)
CAUTION:
All access holes must be
grouted with mortar - after
line or conduit feed to seal
any gaps or cracks around line
feed conduits
Fire Brick Side
Gas or Electric
Conduit
NOTE: Fill Any Gaps
Around Conduit with Mortar