5
For chase enclosures, install the chase top cover (supplied
by others) to the chase enclosure. Cut a hole in the chase
top cover the same diameter as the base of the cone on
the flashing. Attach the Flashing to the top of the chase
cover, sealing with a non-hardening waterproof sealant.
Secure in place with screws or rivets. See
FIG. 10
.
FIG. 8
FIG. 9
Attach the storm collar around the chimney above the
screen of the flashing. Secure in place with the locking
tab and button. Seal around the storm collar with a non-
hardening waterproof sealant. Attach the Termination
Cap to the chimney by sliding the male to female joint
connection together and secure in place with (4) sheet
metal screws provided. See
FIG. 11
.
Attic Insulation Shield:
The Attic Insulation Shield must
be installed where the chimney passes into an attic. Its
purpose is to maintain clearances from loose packed or
blown insulation from the chimney. If an Attic Shield is not
used the chimney needs to be enclosed within a framed
enclosure. Always maintain a 2” air-space clearance to
combustibles. Install the shield as follows:
•
Remove any insulation or debris from attic floor around
the framed opening.
•
Assemble chimney sections above the Firestop to
a height that extends beyond the height of the attic
insulation shield.
•
Slip the Attic Insulation Shield over the chimney until
the base sits squarely on the framed opening.
•
Secure the Attic Insulation Shield to the top of the
framed opening using nails or screws. See
FIG. 8
.
Termination:
NFPA 211, “Standard for Chimneys,
Fireplaces, Vents, and Solid Fuel-Burning Appliances”,
states that chimneys shall extend at least three feet above
the highest point where it passes through the roof of a
building, and at least two feet higher than any portion of a
building within ten feet. See
FIG. 9
.
CHIMNEY
ATTIC
INSULATION
SHIELD
NAILS OR
SCREWS
FLOOR/
CEILING
FIRESTOP
FIG. 10
SCREW OR
RIVET STRAPS
TO FLASHING
CHASE COVER
(SUPPLIED
BY OTHERS)
RADIATION SHIELD
FLASHING
SCREW OR RIVET
TO CHASE COVER
APPLY SEALANT
NAIL TO CHASE
CHASE
CHIMNEY
2 FEET ABOVE ANY POINT WITHIN
10 FEET HORIZONTALLY
3 FEET
MINIMUM
ABOVE
ROOFLINE
FIG. 11
SELF-TAPPING
SCREWS
APPLY SEALANT
FLASHING
STORM COLLAR
TERMINATION