CREATED ON: April 30, 2016

 

 

 

Wiring 

 
System Type : Star/Wye

 

 

 

Keys and Operation 

 

SELECT Key 

PROGRAM MODE

: used to enter into program mode. 

                               : used to select digits. 

 

ADVANCE Key 

PROGRAM Mode

  : used to increase the value by one

 

 

PREVIOUS Key 

PROGRAM Mode

 : used to program previous pages and 

parameters 

RUN Mode            

:  used to view previous parameters 

 

NEXT Key 

PROGRAM Mode

 : used to view next pages and parameters 

RUN Mode            :

  used to view  next parameters 

SCROLL/HOLD Key 

RUN Mode :

 used to scroll/hold the parameters

 

RUN Mode 

 

Once there is power failure, energy, Load/hour, Display Status will be 
saved. 

 

RS485 communication status can be viewed in “DEV ID” 
parameter.”T” for transmit, ”R” for receive & “U” for device ID 
mismatch. 

PROGRAM  Mode 

Program 

page 

Function 

Range 

Factory 

setting 

PASSWd 

0001 to 9999 

1000 

CT-PRI 

1A to 5000A 

CT-SEC 

1A to 5A 

PT-PRI 

110V to 999KV 

415 

PT-SEC 

110V to 500V 

415 

CLR-EN 

Y/N 

dEV-Id 

1 to 247 

001 

bAUd 

2400,4800,9600 

and 19200(bps) 

9600 

ChPASS 

0001-9999 

0001 

 

 

Technical Specification     

Function 

Basic/Energy meter 

Aux. Supply

 

85 to 270 V AC / DC 

Rated Frequency 

50 / 60Hz ±  5% for AC only

 

Power consumption 

< 5 VA / 1W 

 
Input voltage

 

3 Phase 4 wire (R,Y,B,N) 

415 VAC (-40% to +20%) 
110 VAC (-40% to +20%) 

 
Input current

 

Current inputs (AR, AY,

 AB)

 

1A to 5A (to 200%) 

Input Frequency

 

50 Hz, 

±

 2% 

Burden

 

< 0.2 VA per Volts/Amps input 

Accuracy

 

Class 1 / Class 0.5 

Recovery Time

 

2 sec minimum 

Communication

 

RS-485 MODBUS RTU  Protocol 

Meter Constant

 

3200 Pulses / KWh. 

 
Ambient Temperature 

Operation

: -

10°C to +55°C(14°F to 131°F

Storage : -25°C to +80°C(-13°F to  176°F)

 

Humidity 

Up to 95% RH @ 40°C 

 
 

Disposition 

                                                                                                                     

Once the product life is over, you may send back the unit to   EAPL for 
disposition             

 

 
Contact 

Electronic Automation Pvt. Ltd

 

#20, KHB Industrial Area                                                                                                     
Yelahanka, Bangalore -560064

 

Ph: +91-80-28567561/2, /42802345 

 

Email:  

[email protected]

,

 

          

www.eaplindia.com

 

 
 

1, 2, 3, 4

  :  R, Y, B, N

 

5 ,6

          :  No connection 

7,8

           :  A,B (RS 485Communication port) 

9, 10

        :  S1, S2 (R Phase) 

11,12

       :  S1, S2 (Y Phase) 

13,14

       :  S1, S2 (B Phase) 

15,16

       :  Auxilary Supply(85-270 V AC/DC) 

OD RE YN 390011 REV 02/30-04-16

 

Page 2 of 2 