DCPS-6K
Maintenance & Operation Manual
Issue 2.0 Sept-2016
DCPS-6K
Maintenance & Operation Manual
16 /23
LCD
WINDOW
LED
INDICATOR
SELECTION
BUTTON
Figure 3-2.
Control Unit Front View
3.4 Abnormal Actions / Corrective Measures
If the FAIL LED (red) is on while the Rectifier System is powered ON, the alarm status
will be displayed on the LCD window of the control panel and the audible alarm will
sound. Check the alarm satus and take corrective measures.
Table 3-1 Corrective Actions per Alarm (optional, user defined)
No
ALARM
CORRECTIVE MEASURES
Default (List)
Port1
AC input
AC High & Low voltage
Measure actual input voltage using the digital volt
meter. Verify input voltage UV, OV alarm settings.
AC UV : Under 174Vac
AC OV : Over 276Vac
Port2
Output
voltage
Verify default setting of output voltage.
Verify output voltage UV,OV alarm settings.
Verify individual current of unit and check if load
sharing is working correctly (only for the case of
Under voltage fail).
DC OV : Over 58Vdc
DC UV : Under 47.5Vdc
Port3
Rectifier
module
If an inserted rectifier module inserted has any
problem, remove and reinsert it. If it fails again,
replace the module.
UNIT FAIL
(Default.#1~#2, Max #3)
Port4
Environment
(Etc)
Check details using a PC and the Debug port to
check the actual status of the alarm.
Rack. High Temp (80
℃
)
Rack. Sensor fail (open)
Port5
Ext Alarm
Check details using a PC and the Debug port to Digital input Alarm fail