EJECTOR
Figure 3-1. Rectifier Unit Front View
3.2.2 Rectifier Module Removal
Remove the Rectifier Module by pushing in on the top front portion of the ejector
then pull the ejector handle to slide the module out from the shelf assembly
.
3.3 Normal Operation
Status data is displayed on the LCD window of the Control unit. Use the push button
switches on the front panel to edit or display setup values.
3.3.1 Initial Operation Status Check
1)
Rectifier Module (NESPACE-48/2K)
Check that the ON LED is illuminated.
Check that ALARM LED is turned off.
If the FAIL LED is ON, the Rectifier Module is not operating normally. In that case,
check the unit status on the LCD window of the Control unit.
Check that the Rectifier Module fan operates normally (pulls air in from front to
rear).
2)
Controller (NESPACE-KA)
Check that the status indicator “ FAIL” LED (red) is off.
Check that the audible alarm is not activated (it should remain quiet).
Check that alarms are not shown (as activated) on the LCD display and that the
LCD displays the present status correctly.