To enable the DC component inspection
7
To enable the GFCI protection
8
To enable the ISO protection
9
To enable the island protection
10
To enable the buzzer
11
To enable the relay
12
To enable the QU curve
13
To enable the PF curve
14
To enable the Q curve
15
To enable the PU curve
16
To enable the shadow
MPPT mode
6.2.5.8.1 Island Protection
The active anti-islanding protection of the inverters is achieved by shifting the
frequency of the inverter away from nominal conditions in the absence of a
reference frequency (frequency shift). It is enabled by default.
6.2.5.8.2 Volt-var Response Mode
The QU Curve is enabled by default. The volt-var response mode changes the
reactive power absorbed or supplied by the inverter in response to the
voltage at its grid-interactive port. The diagram and table below are the
response mode required for the volt–var response according to the standard
of AS/NZS 4777.2:2020.
Shadow MPPT:
PF CURVE
QU CURVE
ISO Prot
DCI Prot
GFCI Prot
Island Prot
Buzzer Enabled
Relay Check
Q CURVE
QU CURVE
ON
PU CURVE