83
17.3.8
Power Supply Indicators
Power On:
1x
Green LED
17.3.9
Hub Connectors
UltraBUS:
4x
RJ45
Ethernet:
4x
RJ45 Connector 10/100/1000Mb
USB:
2x
USB Type-A Socket
Auxiliary Power/Comms:
2x
6 Pin Lemo 1B
Power In:
1x
Neutrik 8 Pin speakON
Mobile Comms:
2x
SMA
Wi-Fi:
2x
RP-SMA
VGA:
1x
Standard Female three row DE-15
RS485:
1x
Male DB9
RS232:
1x
Male DB9
SCADA/Alarm Volt Free Output:
2x
Header Weidmuller SL 3.5 - 6 pin
SCADA/Isolated Inputs:
1x
Header Weidmuller SL 3.5 - 4 pin
Chassis Earth:
1x
M4 Stud
17.3.10
Power Supply Connectors
Power Out:
1x
Neutrik 8 Pin speakON
Power In:
1x
Neutrik powerCON TRUE1
17.3.11
Hub Volts Free Contacts
Type:
4x
Fully isolated SPDT
Switching Voltage:
AC/DC 5V
–
48V
Switching Current:
AC/DC 10mA
–
5A
Connector:
2x
Weidmuller BL 3.5/4, Socket Block, Screw Terminals
17.3.12
Hub Isolated Inputs
Type:
2x
Opto-Isolated
Switching Voltage:
12V
–
90V DC
Connector:
1x
Weidmuller BL 3.5/4, Socket Block, Screw Terminals
17.3.13
Dimensions
Size W x L x D
382mm x 260mm x 100mm (15 x 10.2 x 3.9 inches)
Hub Unit Weight:
3.6kg (7.9 lbs)
Power Supply Weight:
4.2kg (9.2 lbs)
17.3.14
Environmental
Operating Temperature:
0
–
40°C with 3G Modem
0 - 50°C without 3G Modem
Humidity:
0
–
90% RH Non-condensing
IP Rating:
30
17.3.15
EMC
Safety Class:
I
EMC Immunity:
Industrial Levels
EMC Emissions:
Industrial Levels
Summary of Contents for UltraTEV Monitor
Page 1: ......
Page 2: ......
Page 3: ...UltraTEV Monitor Operating Manual Product Code UTM2 Version 4 October 2016...
Page 4: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 1...
Page 78: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 75...
Page 95: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 92 27 Notes...
Page 112: ......