E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D199-00-001-IS

 

Issue 7

 

13-05-22

 

 

Sheet 2 of 8

 

 

2)  Warnings 

 

 

 

  DO NOT OPEN WHEN AN EXPLOSIVE

 

ATMOSPHERE IS 

PRESENT. 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD. 

  ALL ENTRIES M20 X 1.5MM. 

  USE  SUITABLE  RATED  CABLES  AND  CABLE  GLANDS 

IF  TEMPERATURE  EXCEEDS  AS  PER  STANDARDS 
INDICATIONS BELOW. 
FOR ATEX / IECEx

 & UKEx 

STANDARDS: 

70ºC AT ENTRY OR 80ºC AT BRANCHING POINT. 

FOR NEC / CEC STANDARDS: 

60ºC AT ENTRY OR 60ºC AT BRANCHING POINT. 

 

3)  Marking & Rating Information 

 

All  units  have  a  rating  label,  which  carries  the  following 
important information. 

 

Products  may  have  further  approvals,  see  E2S  website  for 
further details. 
 

3.1.  ATEX / IECEx & UKEx Ratings 

 

Standards 

EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): 

Explosive Atmospheres - Equipment. General requirements 

EN60079-1:2014 / IEC60079-1:2014 (Ed 7): 

Explosive Atmospheres - Equipment protection by 
flameproof enclosures "d" 

EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment dust ignition protection 
by enclosure "t" 

Model No: 

Rating 

STExS1: 
DC024 
AC230 

Ex db IIC T6 Gb Ta -50°C to +65°C 
Ex db IIC T5 Gb Ta -50°C to +70°C 
Ex db IIIC T82°C Db Ta -50°C to +70°C 

 

Certificate No.    

DEMKO 16 ATEX 1466X 
IECEx ULD 16.0017X 
UL21UKEX2019X 

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

 

2813 

UKCA Marking and 
Notified Body No. 

 

0518 

 
 
 
 
 
 
 
 
 
 
 

3.2.  NEC / CEC Ratings 

 

 

 
Gas Class I 
 
All models are approved for use as Alarm Horns also comply 
with the following standards for signaling equipment: 
 

UL464A & CSA C22.2 NO. 205-17 

 

NEC Class / Zone Ratings US Codes 

 

Standards 

UL 60079-0 (Ed. 7) 04/15/2020 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-1 (Ed. 7) 2015 

Explosive Atmospheres - Part 1: Equipment Protection by 
Flameproof Enclosures 'd' 

Ratings 

STExS1: 
DC024 
AC230 

Class 1 Zone 1 AEx db IIC T5 Gb Ta -50°C to +70°C 
Class 1 Zone 1 AEx db IIC T6 Gb Ta -50°C to +65°C 

 

Installation must be carried out in compliance with the 
National Electrical Code. 

 
CEC Class / Zone Ratings Canada 
 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016 

Electrical Apparatus for Explosive Gas Atmospheres - Part 1: 
Flameproof Enclosures 'd' 

Rating 

STExS1: 
DC024 
AC230

 

Ex db IIC T5 Gb Ta -50°C to +70°C 
Ex db IIC T6 Gb Ta -50°C to +65°C 

 

Installation must be carried out in compliance with the 
Canadian Electric Code. 

 
NEC & CEC Class / Division Ratings for US / Canada, 
USL CNL 
 

Standards 

UL464A (Ed. 1) 2017 

Standard for Audible Signal Appliances for General 
Signalling Use  

CSA C22.2 No. 205-17 (Ed. 3) 2017 

Signal Equipment 

Rating 

STExS1: 
DC024 
AC230

 

Class I Div 2 Group ABCD T5 Ta -50°C to +70°C 
Class I Div 2 Group ABCD T6 Ta -50°C to +65°C 

 

Installation must be carried out in compliance with the 
National Electric Code / Canadian Electric Code. 

 

Summary of Contents for STExS1

Page 1: ...A 48Vdc 115mA STExS1RAC230 115Vac 73mA 100 240Vac 50 60Hz 80mA 110 105 230Vac 48mA STExS1FDC024 12Vdc 221mA 11 5 54Vdc 221mA 115 110 24Vdc 185mA 48Vdc 115mA STExS1FAC230 115Vac 73mA 100 240Vac 50 60Hz...

Page 2: ...Marking and Notified Body No 2813 UKCA Marking and Notified Body No 0518 3 2 NEC CEC Ratings Gas Class I All models are approved for use as Alarm Horns also comply with the following standards for sig...

Page 3: ...N60529 5 Special Conditions for Safe Use Repair of the flameproof threaded joints and cemented joints is not permitted Figure 1 Flame Path The plastic horn is not anti static and the metallic enclosur...

Page 4: ...xplosive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the nec...

Page 5: ...ranching point temperature may exceed 80 C and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated below Table 2 ATEX IECEx UKEx...

Page 6: ...n for AC Units Figure 7 AC PCBA SPL Configuration 8 2 Stage Switching Polarity DC Units Switching from positive switching default to negative switching DC Only NOTE Max supply is 33V DC if higher DC v...

Page 7: ...V See documents D190 06 005 for AC schematic diagrams 1a AC Single Stage Configuration 1 1b AC Three Four Stage Configuration 1 2 AC Two Three Stage Voltage Free Activation Configuration K Table 4 Sum...

Page 8: ...rrent relevant standards ATEX IECEx UKEx Requirements Only EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electric...

Reviews: