Ingress Protection 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required,  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. A minimum ingress protection rating of IP6X 
must  be  maintained  for  installations  in  explosive  dust 
atmospheres. 
For combustible dust applications, the cable entry device and 
blanking elements shall be in type of explosion protection and 
shall have an IP 6X rating 
 
For use in Class I Division II locations, in order to maintain the 
db  type  protection,  flameproof  conduit  seals  and/or  cable 
glands must be used. 
 

Adapters 

 
The STEx Beacon Range can be supplied with the following 
types of adapters: 
 

M20 to ½” NPT

 

M20 to ¾” NPT

 

M20 to M25 

 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any  other  adapters  used  must  be  suitably  rated  as  per  the 
applicable standards. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 

8)  Flash Pattern Settings 

 
6.1 Flash Rate Setting 

 

 

 

The STExB2 beacons can produce different flash patterns as 
shown in Table 2. The flash patterns are selected by operation 
of the flash setting DIP switch on the PCBA (See Fig 6). 
 

 

Figure 6: DIP Switch Location. 

 
 
 
 

Switch 

Setting

 

S1 Mode

 

00 

1Hz (60FPM) 

01 

1.33Hz (80FPM) 

10 

1.5Hz (90FPM) 

11 

Double Flash 

Table 3: Switch Positions for Flash Patterns 

 

9)  End of Line Monitoring (DC Units) 

 
All DC units have a blocking diode fitted in their supply input 
lines.  An  end  of  line  monitoring  diode  or  an  end  of  line 
monitoring resistor can be connected across the +ve and 

ve 

terminals in the flameproof chamber. If an end of line resistor 
is used it must have a minimum resistance value of 3k3 ohms 
and  a  minimum  wattage  of  0.5W  or  a  minimum  resistance 
value of 500 ohms and a minimum wattage of 2W. 
 

10) Interchangeable & Spare Parts 

 

 

 

The beacon lens is interchangeable, contact European Safety 
Systems  Ltd  for  a  replacement  lens  available  in  various 
colours. 
 
The  guard  is  an  integral  part  of  the  protection  and  must  be 
reassembled exactly the same way as it was disassembled. 
 
To change the lens, unscrew the M5 socket head screws and 
remove the M5 screws, M5 spring & flat washers.  
 

 

Figure 7: Removal of Lens.

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Warning 

 

Hot surfaces. External surfaces 

and internal components may be hot after 
operation, take care when handling the 
equipment. 

 Warning 

 high-intensity light source. 

Avoid looking directly at the light source for 
extended periods of time. 

Summary of Contents for STExB2X05DC012

Page 1: ...Vac 110 120Vac 50 60Hz 140mA 200mA STExB2X05AC230 230Vac 220 240Vac 50 60Hz 70mA 100mA STExB2X10DC024 SIL 24Vdc 20 28Vdc 605mA 710mA STExB2X10DC048 48Vdc 42 54Vdc 230mA 250mA STExB2X10AC115 115Vac 110...

Page 2: ...4 X15DC048 Ex db IIC T4 Gb Ta 50 C to 70 C Ex tb IIIC T127 C Db Ta 55 C to 70 C STExB2 X15AC115 X15AC230 Ex db IIC T3 Gb Ta 50 C to 70 C Ex db IIC T4 Gb Ta 50 C to 65 C Ex tb IIIC T131 C Db Ta 55 C to...

Page 3: ...th the National Electric Code Canadian Electric Code 4 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification...

Page 4: ...les to the beacon it is necessary to remove the flameproof cover to gain access to the flameproof chamber To access the Ex d chamber loosen the M4 grub screw on the beacon cover Open the enclosure by...

Page 5: ...h large cross sectional areas such as 2 5mm Earthing Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the ea...

Page 6: ...sser 8 Flash Pattern Settings 6 1 Flash Rate Setting The STExB2 beacons can produce different flash patterns as shown in Table 2 The flash patterns are selected by operation of the flash setting DIP s...

Page 7: ...Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 1...

Page 8: ...R DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT S...

Page 9: ...NGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO...

Page 10: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Page 11: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Reviews: