E2S GNExL2 Instruction Manual Download Page 3

__________________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D157-00-201        Issue 3     25-06-20                                  Sheet 3 of 4

                                                                                     

(3) 

 

 
On  completion  of  the  cable  wiring  installation  the  flameproof 
joints  should  be  inspected  to  ensure  that  they  are  clean  and 
that  they  have  not  been  damaged  during  installation.  Also 
check  that  the  ‘O’  ring  seal  is  in  place.  When  replacing  the 
flameproof  cover  ensure  that  it  is  tighten  fully  with  tool 
provided. 

 

9) 

Power Amplifier Selection 

 

It  is  important  that  the  loudspeakers  are  connected  to  power 
amplifiers that have outputs that are compatible to the type of 
loudspeaker  being  used.  Loudspeakers  with  a  70V  or  100V 
line matching transformer fitted must be connected to a power 
amplifier  with  a  70V  or  100V  line  output.  Low  impedance  8 
ohm or 16 ohm loudspeakers must be connected to amplifiers 
with  a  suitable  low  impedance  output.  When  selecting  the 
cable size consideration must be given to the current that each 
unit  draws,  the  number  of  loudspeakers  on  the  line  and  the 
length of the cable run. 
 
The following table shows the range of loudspeakers:- 

 

Unit Type 

Input  

 

Wattage   

Max. 

 

 

 

 

 

 

I/P Volts

 

 
GNExL2   

100V Line 

25W 

 

100V 

GNExL2   

70V line   

25W 

 

70V 

GNExL2   

8 ohm 

 

25W 

 

14.14V 

GNExL2   

16 ohm   

25W 

 

20V 

 
GNExL1   

100V Line 

15W 

 

100V 

GNExL1   

70V Line   

15W 

 

70V 

GNExL1   

8 ohm 

 

15W 

 

10.95V 

GNExL1   

16 ohm   

15W 

 

15.49V 

 

The above table also shows the maximum AC signal voltages 
at which the loudspeakers can be operated. 
 
The current levels taken by the each loudspeaker will depend 
on which output tapping has been selected (see section 13 of 
this  instruction  manual).  GNExL2  70V  and  100V  Line  units 
have output levels of 25W, 12.5W, 6W and 2W; GNExL1 70V 
and 100V Line units have output levels of 15W, 7.5W, 3W and 
1W. 
 
 
 

10) 

  Cable Selection 

 

When selecting the cable size consideration must be given to 
the  input  current  that  each  unit  draws  (see  table  2  of  4),  the 
number of loudspeakers on the line and the length of the cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity to provide the input current to all of the loudspeakers 
connected to the line.  
 

SAFETY WARNING: If temperature exceeds 70ºC at entry or 
80ºC at branching point use suitably rated cable and cable 
glands. 

 

11) 

  Earthing 
 

Both  AC  and  DC  loudspeaker  units  must  be  connected  to  a 
good  quality  earth.  The  units  are  provided  with  external 
earthing  terminals  which  are  both  located  on  the  terminal 
chamber section of the unit (see figures 2 and 3).  
 

 

When using the external earth terminal a cable crimp lug must 
be used.  The cable lug should be located between the two M4 
stainless steel flat washers. The M4 stainless steel spring 
washer must be fixed between the outer flat washer and the 
M4 stainless steel nut to ensure that the cable lug is secured 
against loosening and twisting.  

 

 

12) 

 Cable Glands

 

 

The  GNExL2  and  GNExL1  sounders  have  dual  cable  gland 
entries which have an M20 x1.5 entry thread as standard. Only 
cable  glands  approved  for  Ex  ‘d’  applications  can  be  used, 
which  must  be  suitable  for  the  type  of  cable  being  used  and 
also meet the requirements of the Ex ‘d’ flameproof installation 
standards EN 60079-14:2008 / IEC60079-14:2007. 

 
SAFETY WARNING: If temperature exceeds 70ºC at entry or 
80ºC at branching point use suitably rated cable and cable 
glands. 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable gland.  
 
When  only  one  cable  entry  is  used  the  other  one  must  be 
closed with an Ex ‘d’ flameproof blanking plug, which must be 
suitably approved for the installation requirements.  
 
 
 

Figure 2 

Figure 3 

Reviews: