background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D156-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 9 of 15

 

 

Power  relay  RLY1-1  will  be  open  whilst  SIL  2  relay  RLY1-2 
will be closed contact between terminals 1 & 2. 
 
The SIL 2 unit will also check for signal polarity. 
 
If a fault is found the SIL 2 unit will go into 

Fault mode

 
If power is disrupted the SIL 2 unit will go into 

Fault mode

, in 

fault  mode  the  Power  relay  RLY1-1  will  close  whilst  SIL  2 
relay  RLY1-2  will  become  an open  circuit  between  terminals 
1 & 2. 
 

 

Fault modes

 - The fault modes listed in sections 13-1 & 13-2 

will result in a change of state for relays RLY1-1 and RLY1-2. 
 
In fault mode the  Power relay RLY1-1 will close whilst SIL 2 
relay  RLY1-2  will  become  open  be  circuit  between  terminals 
1 & 2. 

 

13-1 Beacon Failure 

 

 

Flash Failure 

 No flash detected. 

 

Beacon  Controller  Failure 

  No  flash  trigger  pulse 

detected. 

 

Flash  Rate  Failure 

  Regular  1  Hz  flash  cycle 

erratic. 

 

13-2 Power Failure / SIL 2 Failure 

 

 

SIL  2  Controller  Failure 

  Internal  function  and 

system checking flags fault. 

 

Rapid  Power  Cycling 

  System  indicates  power 

instability. 

 

Total Power Failure.  

 
It is possible to reset these faults if they were transitory. 
 
Resetting  Failure  (by  power  cycling)  -  It  is  possible  that  the 
SIL  2  unit  can  be  reset  by  powering  the  unit  off  for  a  period 
greater  than  20  seconds.  On  restarting  the  unit  and  running 
through the commissioning cycle the fault may clear. 
 
Resetting Failure (by Hard Reset) - It is possible that the SIL 
2 unit can be reset by hard resetting the unit using the reset 
jumper  within  the  unit  (see  section  15-4)  on  hard  resetting. 
On restarting the unit and running through the commissioning 
cycle,  the  fault  may  clear.  It  is  necessary  to  run  the  test 
function cycle again to see if the fault is still evident. 
 
If the hard reset process does not correct the latched fault the 
alarm horn sounder may require further investigation, please 
contact your local E2S representative. 
 
 
 
 
 
 
 

Commissioning  System  -  Functional  start-up  of  System 
(Normally in reverse polarity mode) 

 
When  Commissioning  system  the  power  must  not  be 
disrupted to the SIL 2 Unit within the 

unit’s 

initialization cycle 

which is 

5 seconds

 
Once  past  this  period  the  SIL  2  system  is  fully  operational 
and  will  be  in  monitoring  the  beacon  and  power  in  Standby 
mode. 
 
The relay RLY1-2 on the SIL 2 unit will only remain open for a 
maximum  of  1  second  on  commissioning  start-up.  RLY1-2 
will  subsequently  close  contacts  1  &  2  indicating  healthy 
operation. Contact 1 & 2 will only remain open in the event of 
a fault or a loss of power. 
 

System Testing (Active Mode normal polarity) 
 

The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to normal mode to enable 
an active system for beacon functional testing. 
 

Important

:  -  The  polarity  must  be  held  in  active  mode  for  a 

period in excess of 

15 seconds

 to ensure a full system check 

is performed. 
 
Once  the  test  period  has  been  completed  the  unit  can  be 
switched back to standby mode by reversing the polarity. 
 
If  no  faults  have  been  found  during  the  test  the  relays  will 
remain in steady state. 
 
The SIL 2 unit will continue to monitor the power and module 
function. 
 

Important

:  -  The  automated  test  cycle 

must

  be  undertaken 

on  at  least  a  weekly  basis  to  maintain  the  SIL  2  units 
reliability. 
 

System Activation (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby 
mode  until  the  polarity  is  changed  to  Active  mode  to  enable 
an  active  system  for  beacon  to  function  as  a  warning 
signaling device. 
 

Important

  :-  The  polarity  must  be  held  in  active  mode  for  a 

period in excess of 15 seconds to ensure a full system check 
is  performed  whilst  in  alarm  mode,  although  it  is  expected 
that during a system activation this period will be significantly 
greater. 
 

Note

 :- The fault indication signal on TB1 can take up to 1.5 

seconds to indicate system fault.

 

 
 
 
 
 
 

 
 
 
 

Summary of Contents for GNExB2X05 Series

Page 1: ... AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER STANDARDS INDICATIONS BELOW FOR ATEX IECEx UKEX STANDARDS 70ºC AT ENTRY OR 80ºC AT BRANCHING POINT FOR NEC CEC STANDARDS 60ºC AT ENTRY OR 60ºC AT BRANCHING POINT 3 Marking Rating Information All units have a rating label which carries the following important information Unit Model Voltage Range Nominal Voltage Max Current See Table 1 for electrical r...

Page 2: ...t in compliance with the National Electric Code CEC Class Zone Ratings Canada Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 No 60079 1 Ed 3 2016 Electrical Apparatus for Explosive Gas Atmospheres Part 1 Flameproof Enclosures d Rating GNExB2X05 DC024 S Ex db IIC T5 Gb Ta 50 C to 70 C Ex db IIC T6 Gb Ta 50 C to 60 C GNExB2X1...

Page 3: ...emented joints is not permitted Figure 1 Flame Path The enclosure is non conducting and may generate an ignition capable level of electrostatic charges under certain extreme conditions The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build up of electrostatic charges on non conducting surfaces The stainless...

Page 4: ...osive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training NEC CEC Installation Standards Cautions Attention Installation must be carried out by an electrician in compliance with the National Electrical Code NFPA 70 or CSA 22 1 Canadian Electrica...

Page 5: ...ºC or the cable branching point temperature may exceed 60ºC and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated below Table 3 NEC CEC Min Ratings of Cables Cable Glands Cable Glands Blanking Plugs Appropriate cable glands to be customer supplied ATEX IECEx UKEx Requirements Only The cable gland entries have an M20 x 1 5 ent...

Page 6: ...IP Switch Location Switch Setting S1 Mode SIL Approved 00 1Hz 60FPM Yes 01 1 33Hz 80FPM No 10 1 5Hz 90FPM No 11 Double Flash No Table 4 Switch Positions for Flash Patterns 9 End of Line Monitoring DC Units All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the...

Page 7: ...ul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance Units must not be opened while an explosive...

Page 8: ... and Function The SIL 2 Beacon Unit Monitors Standby mode and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system The beacon will after commissioning remain powered in Standby mode reverse polarity until the beacon is required to operate When the signalling device is required to operate beacon the polarity is chan...

Page 9: ...t correct the latched fault the alarm horn sounder may require further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must not be disrupted to the SIL 2 Unit within the unit s initialization cycle which is 5 seconds Once past this period the SIL 2 system is fully ope...

Page 10: ...though it is highly recommended that the unit is wired as stated in section 15 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 15 3 places TB1 Current sense resistor in circuit J2 Header Fault Resistor FR Shown in factory default position A see section 15 3 removes power supply terminal block Fault resistor relay RLY 1 1out of circuit J7 He...

Page 11: ...om the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Current Sense Resistor value Current drawn mA 3 3kΩ 7 2mA On fault mode current drops to 0 as circuit goes open Figure 13 Schematic of SIL 2 system wiring for fault detection in standby and active m...

Page 12: ...ults and faults occur If multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 621 IS available from the E2S website I Total Current drawn Current drawn from Fault Resistor Current drawn from Customer EOL resistor Current drawn from SIL board Standby Mode Total Current drawn No Fault 0mA ...

Page 13: ... Position B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 16 J2 Header pin positions Fault Resistor FR 15 4 SIL 2 Hard Reset Function Power down the unit completely for a minimum of 30 seconds Move the hard reset header pin Jumper J7 to reset position B shown Then power the unit for a minimum of 5 seconds Power down the unit f...

Page 14: ...1 Random Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input by lighting a beacon Spurious light output despite no input Integrity in respect of failure to release SIL 2 Total Failure rate 0 35 pmh Hazardous failure rate revealed 0 287 pmh Hazardous failur...

Page 15: ...cified when ordering The values of resistors available are shown in table 6 below Code Resistor Value Default resistor coding is as follows GNExB2X05DC024AS1S1R A AFZ Example of a custom requirement resistor coding GNExB2X05DC024AS1S1R A GEF Where the FR Fault Resistor is G 3 9 kΩ CSR Current Sense Resistor is E 2 7 kΩ EOL End Of Line resistor is F 3 3 kΩ A 2 2 kΩ B 1 0 kΩ C 1 5 kΩ D 1 8 kΩ E 2 7 ...

Page 16: ...TERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2022 23 09 2022 23 09 2022 D1xB2 GNExB2 STExB2 SIL2 DC XENON BEACON WIRING DIAGRAM INTRODUCTION INTRODUCTION 1 MA 23 09 2022 SIL2 WIRING DIAGRAM FOR THE FOLLOWING PRODUCTS D1xB2X05DC024 SIL D1xB2X10DC02...

Page 17: ... B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applie...

Page 18: ...r Date and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of th...

Page 19: ...ke Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 ...

Page 20: ...er Date and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of...

Reviews: