FIRE INSTRUCTION & SERVICE MANUAL 

D2xS2-DC024-A UL464 / CAN/ULC-S525 Fire 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D252-00-001-IS-UL

 

Issue A

 

29-08-2023

 

 

Sheet 1 of 1

 

 

 

 

 

 

 
 

Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70, and 
the National Fire Alarm Signaling Code, NFPA 72 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for 
Electrical Installations, Section 32. /  L'installation doit exclusivement être réalisée par du personnel qualifié, conformément 
au code national d'électricité américain, NFPA 70, et le code national d’alarrme incendie et de signalisation NFPA 72 ou 
CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux installations électriques, Section 32 
 
Attention: Disconnect from power source before installation or service to prevent electric shock / Débranchez-le de la source d'alimentation 
avant l'installation ou l'entretien pour éviter tout choc électrique. 
 
Attention: Fire Alarm Device—Do not paint / Ne pas Peinturer—Dispositif D’Alarme 
 
Attention: Do not change factory applied finishes / Ne pas changer le revetement applique en usine 

 
 

 

Type 4 / 4X / 3R / 13, IP66  

 

-55°C to +80°C / -67°F to +176°F 

 

Units should be mounted using at least 2 of the 3-off/4-off ø7mm holes in the mounting bracket. 

 

The Equipment must not be installed with the horn facing upwards of horizontal. 

 

D2xS2FDC024-A is  approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 & CAN/ULC-S525) and produces a minimum sound 
pressure level of P2: US: 94.9dB(A); CA: 101.6dB(A) / P3: US: 96.96dB(A); CA: 103.6dB(A) at 10 feet, (figures @ worst case voltage 11.5V). 

 

D2xS2FDC024-A is approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 & CAN/ULC-S525) and produces a minimum sound 
pressure level of P2: US: 98.42dB(A); CA: 105.2dB(A) / P3: US: 104.11dB(A); CA: 110.6dB(A)  at 10 feet, (figures @ 24V). 

 

D2xS2HDC024-A is  approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 & CAN/ULC-S525) and produces  a minimum sound 
pressure level of P2: US: 95.51dB(A); CA: 103.8dB(A) / P3: US: 97.11dB(A); CA: 107.9dB(A) at 10 feet, (figures @ worst case voltage 11.5V). 

 

D2xS2HDC024-A is approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 & CAN/ULC-S525) and produces a minimum sound 
pressure level of P2: US: 100.2dB(A); CA: 108.5dB(A) / P3: US: 104.02dB(A); CA: 114.9dB(A) at 10 feet, (figures @ 24V). 

 

If a high IP (Ingress Protection) rating is required then a suitable sealing washer or O-ring must be fitted under any cable gland or blanking device with metric threads. 

 

To maintain the enclosure rating, the cable entries must be fitted with suitably rated cable entry and/or blanking devices or suitably sized conduit during installation. If 
entries are fitted with adaptors they must be suitable for the application. 

 

Units can be located indoor or outdoor wet use, wall or ceiling mounted and there are no limitations on orientation. 

 

For Fire Alarm applications, the Sounder Volum\e must be at the highest setting, (see volume control section). For fire alarm use, Tone 12 as shown below must be 
selected: 

 
 
 
 
 
 

 

Connection Terminals: Pluggable, 0.2 - 2.5mm

2

 / AWG24 - AWG12 

 

Terminal Tightening torque 0.4Nm/3.5lb-in.

 

 

 

 
 

D2xS2FDC024-A Sounder Directional Characteristics for 

Canadian Fire CAN/ULC-S525 

 

OSPL 

Horizontal Axis 

Vertical Axis 

-3dB(A) 

+16.3° / -10° 

+/-10° 

-6dB(A) 

+40° / -13.3° 

+/-15° 

D2xS2HDC024-A Sounder Directional Characteristics for 

Canadian Fire CAN/ULC-S525  

 

OSPL 

Horizontal Axis 

Vertical Axis 

-3dB(A) 

+/-10° 

+/-10° 

-6dB(A) 

+/-15° 

+/-35° 

Surge Current Ratings for use in fire alarm systems 

Model 

Nominal 
Voltage 

Voltage Range 

Initial Peak 

Initial RMS 

  Repetitive Peak 

   Repetitive RMS 

   Operating RMS 

D2xS2FDC024-A 
D2xS2HDC024-A  

24V dc   

11.5 - 54V dc   

P3:1910 mA 

P3:922 mA  

  P3: 625 mA  

   P3:522 mA  

   P3:603 mA  

1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal 
Pattern

Stage 1
Set DIP
SW 1
Tone No.

Tone Description

Tone Visual

Stage 1 & 2
DIP SW 1/2

 Settings

1 2 3 4 5 6

Stage 3
Set DIP

SW 1

(S3)

Stage 4
Set DIP

SW 1

(S2 + S3)

12

1 1 0 1 0 0

1000Hz 0.5s

0.5s

0.5s

0.5s

0.5s

1s

1

8




S2 
S3 

 

S2 

S1 

  

P2 

(D2xS2)

 

  

P3 

(D2xS2)

 

Summary of Contents for D2xS2F Series

Page 1: ...above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electrical Ratings 2 Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN W...

Page 2: ...ition 7 EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Edition 5 1 EN 60079 31 2014 IEC 60079 31 2022 Edition 3 Model No Rating D2xS2FDC024 D2xS2HDC024 Ex ec IIC T3 Gc Ta 55 C to 75 C Ex ec IIC T4 Gc Ta...

Page 3: ...ys be fitted d Replace the cover of the unit taking care not to damage the threads Tighten fully 6 3 Access to the Enclosure Fig 2 Accessing the enclosure To access the chamber loosen the M4 grub scre...

Page 4: ...lands or blanking plugs A minimum ingress protection rating of IP54 must be maintained for installations in explosive gas atmospheres and IP6X must be maintained for installations in explosive dust at...

Page 5: ...e 1 DIP switch setting Following table Table 3 is a summary of DC D252 06 001 AC D252 06 005 wiring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Sta...

Page 6: ...duct option V when ordering Spare part code for field installation SP78 0001 Figure 10 End of Line Resistor placement Optional 12 Way Terminal Module 10 Maintenance Overhaul and Repair Maintenance rep...

Page 7: ...with suitably rated cable glands or stopping plugs EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire si...

Page 8: ...4V D2xS2HDC024 A is approved for use as an audible signal appliance for fire alarm use Public Mode UL464 CAN ULC S525 and produces a minimum sound pressure level of P2 US 95 51dB A CA 103 8dB A P3 US...

Page 9: ...1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0...

Page 10: ...MONITORING RESISTOR CUSTOMER SUPPLIED 24V MAX SYSTEM 3K9 MIN 0 5W MIN OR 1K MIN 2 0W MIN 48V MAX SYSTEM 15K MIN 0 5W MIN OR 3K9 MIN 2 0W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 11: ...e OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED RECOMMENDED MINIMUM VALUES...

Page 12: ...to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 C...

Page 13: ...2 A B D252 06 005 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2...

Page 14: ...urance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812...

Page 15: ...the components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure r...

Page 16: ...Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quali...

Page 17: ...e components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rate...

Page 18: ...Page left Intentionally blank...

Page 19: ...Page left Intentionally blank...

Page 20: ...Page left Intentionally blank...

Reviews: