background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D252-00-001-IS

 

Issue 1

 

21-12-2023

 

 

Sheet 4 of 7

 

 

 

Fig. 4 Earth Locations 

 
Please note that for AC supply voltage product versions the Earth 
terminal on the PCBA does not provide an earth connection to the 
product enclosure. The enclosure must be independently earthed 
using either the external or internal earth fixing point, (see fig 4 and 
notes below). 
 
The unit has both a primary internal and secondary external earth 
fixing point. 
  
Internal earthing connections should be made to the Internal Earth 
terminal in the base of the housing using a ring crimp terminal to 
secure the earth conductor under the earth clamp. The earth 
conductor should be at least equal in size and rating to the incoming 
power conductors but at least a mini mum of 0.82mm2 / 18AWG in 
size. 
 
External earth connections can be made to the M5 earth stud (see 
Fig. 4), using a ring crimp terminal to secure the earth conductor 
to the earth stud. The external earth conductor should be at least 
4mm

2

 in size. 

  
The external earth crimp ring should be located between the two 
M5 plain washers provided and securely locked down with the M5 
spring washer and M5 nut. 

 

7.4 

Cable Glands, Blanking Elements & Adapters 

 
Ingress Protection 

 

If a high IP (Ingress Protection) rating is required then a suitable 
sealing washer must be fitted under the cable glands or blanking 
plugs.  A  minimum  ingress  protection  rating  of  IP54  must  be 
maintained  for  installations  in  explosive  gas  atmospheres  and 
IP6X  must  be  maintained  for  installations  in  explosive  dust 
atmospheres. 
 
To maintain the ingress protection rating and mode of protection, 
the  cable  entries  must  be  fitted  with  suitably  rated  cable  entry 
and/or blanking devices during installation. 
  
If entries are fitted with adaptors they must be suitably rated for 
the application. Fitting of blanking elements into adaptors is not 
permitted. 

 

Adapters 

 
The D2xS2 sounder range can be supplied with the following types of 
adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 

It  is  important  to  note  that  stopping  plugs  cannot  be  fitted  onto 
adapters, only directly onto the M20 entries.  

 
 
 
 
 
 
 
 
 
 

For high ambient temperatures the cable entry temperature may 
exceed 70ºC or the cable branching point temperature may exceed 

80ºC and therefore suitable heat resisting cables and cable glands 
must be used, with a rated service temperature at least as 
stated below: 
 

 

8)  Settings 

 

Following  illustrations  show  the  settings  available  for  D2xS2  Alarm 
Horn Sounders. See schematic diagram D252-06-001 for details. 

 

8.1 

Configuration 

 

See  Table  1  for  product  power  supply  and  Sound  Pressure  Levels 
(SPL). 

 

Configuration for DC Units 

 

 

Fig 5: DC PCBA. 

 

Configuration for AC Units 

 

 

Fig 6: AC PCBA . 

 
 
 
 
 

 
8.2 

Stage Switching Polarity (DC Units) 

 

Ambient Temp. (°C) 

55 

60 

65 

70 

75 

D2xS2FDC024 / D2xS2HDC024   
Min. Rating of cables and cable glands (°C) 

70 

75 

80 

85 

D2xS2FAC230 / D2xS2HAC230   
Min. Rating of cables and cable glands (°C) 

70 

75 

80 

85 

90 

Internal Earth 
Marked with G 

External Earth 

  

  

(default) 

(default) 

Summary of Contents for D2xS2F Series

Page 1: ...above are for the 440Hz Continuous tone nominal input voltage Nominal current at nominal voltage Table 1 Electrical Ratings 2 Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN W...

Page 2: ...ition 7 EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Edition 5 1 EN 60079 31 2014 IEC 60079 31 2022 Edition 3 Model No Rating D2xS2FDC024 D2xS2HDC024 Ex ec IIC T3 Gc Ta 55 C to 75 C Ex ec IIC T4 Gc Ta...

Page 3: ...ys be fitted d Replace the cover of the unit taking care not to damage the threads Tighten fully 6 3 Access to the Enclosure Fig 2 Accessing the enclosure To access the chamber loosen the M4 grub scre...

Page 4: ...lands or blanking plugs A minimum ingress protection rating of IP54 must be maintained for installations in explosive gas atmospheres and IP6X must be maintained for installations in explosive dust at...

Page 5: ...e 1 DIP switch setting Following table Table 3 is a summary of DC D252 06 001 AC D252 06 005 wiring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Sta...

Page 6: ...duct option V when ordering Spare part code for field installation SP78 0001 Figure 10 End of Line Resistor placement Optional 12 Way Terminal Module 10 Maintenance Overhaul and Repair Maintenance rep...

Page 7: ...with suitably rated cable glands or stopping plugs EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire si...

Page 8: ...4V D2xS2HDC024 A is approved for use as an audible signal appliance for fire alarm use Public Mode UL464 CAN ULC S525 and produces a minimum sound pressure level of P2 US 95 51dB A CA 103 8dB A P3 US...

Page 9: ...1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0...

Page 10: ...MONITORING RESISTOR CUSTOMER SUPPLIED 24V MAX SYSTEM 3K9 MIN 0 5W MIN OR 1K MIN 2 0W MIN 48V MAX SYSTEM 15K MIN 0 5W MIN OR 3K9 MIN 2 0W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 11: ...e OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED RECOMMENDED MINIMUM VALUES...

Page 12: ...to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 C...

Page 13: ...2 A B D252 06 005 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2...

Page 14: ...urance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812...

Page 15: ...the components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure r...

Page 16: ...Assurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quali...

Page 17: ...e components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rate...

Page 18: ...Page left Intentionally blank...

Page 19: ...Page left Intentionally blank...

Page 20: ...Page left Intentionally blank...

Reviews: