background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-651-IS

 

Issue 1

 

20-08-22

 

 

Sheet 5 of 8

 

 

 

 

Fig. 6b End of Line Resistor Placement – Sounder 

 

12) 

Settings 

 

12.1 Beacon DIP Switch 

 

Please note that the D2xC2XH1 & D2xC2XH2 beacon PCBAs 
have  a  DIP  Switch  that  is  NOT  customer  configurable.  This 
should only ever be set to ‘00’. 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 7 DIP Switch setting ‘00’ 

 

12.2 Volume Control 

 

The alarm horn output  level of  the  D2xC2  unit can  be set  by 
adjusting  the  volume  control  potentiometer  (see  Fig  9).  For 
maximum output, set the potentiometer fully clockwise. 
 

 

Fig. 9 Location of field controls 

 

12.3 Tone Selection 

.

 

The  D2xC2  alarm  horns  have  64  different  tones.  The  tones 
are  selected  by  operation  of  the  tone  setting  DIP  switches 
(see  Fig.  9)  on  the  PCB.  The  alarm  horns  can  also  be 
switched  to  sound  the  second,  third  and  fourth  stage  alarm 
tones.  The  tone  table  shows  the  switch  positions  for  the  64 
tone  and  which  tones  are  available  for the  second,  third  and 
fourth stages. 

 
 

13) 

Maintenance, Overhaul & Repair 

 

Maintenance, repair and overhaul of the equipment should only 
be carried out by suitably qualified personnel in accordance with 
the current relevant standards: 

 

EN60079-19 
IEC60079-19 

Explosive atmospheres - Equipment repair, 
overhaul and reclamation 

 

EN 60079-17 
IEC60079-17 

Explosive atmospheres - Electrical 
installations inspection and maintenance 

 

To avoid a possible ELECTROSTACTIC CHARGE the unit must 
only be cleaned with a damp cloth. 

 

Units  must  not  be  opened  while  an  explosive  atmosphere  is 
present. 

 

If  opening  the  unit  during  maintenance  operations  a  clean 
environment  must  be  maintained  and  any  dust  layer  removed 
prior to opening the unit. 

Volume 
Control 

Tone Setting 
Switches 1-6 

(See tone 
selection table) 

End Of Line Resistor 

Summary of Contents for D2XC2XH1

Page 1: ...and D2xC2XH2 are certified for use as public mode audible and visual alarm devices in accordance with UL1971 UL1638 UL464 See fire instructions D211 00 651 IS SC UL 3 2 ATEX IECEx UKEx certification S...

Page 2: ...y Enclosure t Rating D2xC2XH1 Ex ec IIC T3 Gc X Ta 40 C to 50 C Ex tc IIIC T75 C Dc Ta 40 C to 50 C D2xC2XH2 Ex ec IIC T2 Gc X Ta 40 C to 50 C Ex tc IIIC T85 C Dc Ta 40 C to 50 C Installation must be...

Page 3: ...ent is not to be mounted with the horn facing upwards Fig 1 Fixing locations 6 2 Access to the Enclosure Warning High voltage may be present risk of electric shock DO NOT open when energised disconnec...

Page 4: ...user wishes to power the strobe separately For further wiring schematics refer to document D211 06 651 10 Earthing The unit has both internal and external earth points please see fig 2 fig 4 Internal...

Page 5: ...the PCB The alarm horns can also be switched to sound the second third and fourth stage alarm tones The tone table shows the switch positions for the 64 tone and which tones are available for the seco...

Page 6: ...22 Sheet 6 of 8 14 Electrical Ratings 14 1 Operating current Consumption Table 6 Electrical Ratings Model Nom Voltage Voltage Range Flash Rate Setting Max operating current D2xC2XH1DC024 24Vdc 20 28Vd...

Page 7: ...s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 3...

Page 8: ...Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz S...

Page 9: ...alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet...

Page 10: ...Dispersion for wall mounting public mode 75 60 45 30 15 0 90 Fig 1 Vertical dispersion angles for wall mounting 55 45 8 18 60 40 7 27 65 35 6 36 70 35 6 36 75 30 5 45 80 30 5 45 85 25 4 55 90 25 4 55...

Page 11: ...ght Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate 0 100 18 18 5 30 90 16 36 35 65 11 82 40 46 8 36 45 34 6 18 50 27 4 91 55 22 4 00 60 18 3 27 65 16 2 91 7...

Page 12: ...fpm 2 28A 1 19A D2xC2XH2DC024 24Vdc 20 28Vdc 1Hz 60fpm 2 76A 1 35A 4 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 101 2 dB A Refe...

Page 13: ...o Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve Stage 4 Apply power to Sounder ve ve Connect Stage 2 and Stage 3 t...

Page 14: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Page 15: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 16: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...

Page 17: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Reviews: