Fault modes

 - The fault modes listed 13-1 & 13-2 below will make the 

SIL 2 unit change the state for relays RLY1-1 and RLY1-2. 
 
In  fault  mode  the  Power  relay  RLY1-1  will  close  whilst  SIL  2  relay 
RLY1-2 will become open circuit between terminals 1 & 2. 
 

13-1 Sounder Failure 
 

 

Tone Failure 

 No Tone detected 

 

Sounder  Controller  failure 

  No  tone  generation  pulse 

detected 

 

Tone Rate Failure 

 Regular tone cycle erratic 

 

13-2 Power Failure / SIL 2 Failure 
 

 

SIL  2  Controller  failure 

  Internal  function  and  system 

checking flags fault 

 

Rapid Power cycling 

 System indicates power instability 

 

Total Power Failure  

 
It is possible to reset these faults if they were transitory. 
 
Resetting Failure (by power cycling) - It is possible that the SIL 2 unit 
can  be  reset  by  powering  the  unit  off  for  a  period  greater  than  20 
seconds.  On  restarting  the  unit  and  running  through  the 
commissioning cycle the fault may clear. 
 
Resetting Failure (by Hard Reset) - It is possible that the SIL 2 unit can 
be  reset  by  hard  resetting  the  unit  using the  reset  jumper  within the 
unit (see section 16-4) on hard resetting. 
On  restarting the  unit  and  running  through  the commissioning cycle, 
the fault may clear. It is necessary to run the test function cycle again 
to see if the fault is still evident. 
 
If the hard reset process does not correct the latched fault the alarm 
horn  sounder  may  require  further  investigation,  please  contact  your 
local E2S representative. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Commissioning  System  -  Functional  start-up  of  System 
(Normally in reverse polarity mode) 

 
When Commissioning system the power must not be disrupted to the 

SIL 2 Unit within the unit’s initialization cycle which is 

5 seconds

 
Once past this period the SIL 2 system is fully operational and will be 
in monitoring the sounder and power in Standby mode. 
 
The  relay  RLY1-2  on  the  SIL  2  unit  will  only  remain  open  for  a 
maximum  of  1  second  on  commissioning  start-up.  RLY1-2  will 
subsequently  close  contacts  1  &  2  indicating  healthy  operation. 
Contact 1 & 2 will only remain open in the event of a fault or a loss of 
power. 
 

System Testing (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby mode 
until the polarity is changed to normal mode to enable an active system 
for sounder functional testing. 
 

Important

: - The polarity must be held in active mode for a period in 

excess of 

15 seconds

 to ensure a full system check is performed. 

 
Once  the  test  period  has  been  completed  the  unit  can  be  switched 
back to standby mode by reversing the polarity. 
 
If  no  faults  have  been found  during  the test  the  relays  will  remain  in 
steady state. 
 
The SIL 2 unit will continue to monitor the power and module function. 
 

Important

: - The automated test cycle 

must

 be undertaken on at least 

a weekly basis to maintain the SIL 2 units reliability. 
 

System Activation (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby mode 
until the polarity is changed to Active mode to enable an active system 
for sounder to function as a warning signaling device. 
 

Important

 :- The polarity must be held in active mode for a period in 

excess of 15 seconds to ensure a full system check is performed whilst 
in alarm mode, although it is expected that during a system activation 
this period will be significantly greater. 

 

Note

  :-  The  fault  indication  signal  on  TB1  can  take  up  to  50 

milliseconds to indicate system fault. 

 
 
 
 
 
 

 
 
 

Summary of Contents for D1xS1RDC024-S

Page 1: ...G IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGI...

Page 2: ...e for electrical ratings of each unit model Certificate No DEMKO 19ATEX2141X IECEx ULD 19 0008X UKEx UL UL21UKEX2132X Epsilon x Equipment Group and Category II 2G II 2D CE Marking and Notified Body No...

Page 3: ...on where it may be subjected to external conditions that might cause a build up of electrostatic charges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclos...

Page 4: ...s on the line and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line DC 0 2 2 5mm2 AWG24 AWG12...

Page 5: ...3 Tone Selection The D1x Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DI...

Page 6: ...0 5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads s...

Page 7: ...ing DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted cor...

Page 8: ...perates as part of a SIL 2 system The sounder will after commissioning remain powered in Standby mode reverse polarity until the sounder is required to operate When the signaling device is required to...

Page 9: ...rity mode When Commissioning system the power must not be disrupted to the SIL 2 Unit within the unit s initialization cycle which is 5 seconds Once past this period the SIL 2 system is fully operatio...

Page 10: ...under check on pattern generation and signal output checks Important Only tones use tones that are stated as SIL 2 approved for the SIL 2 application Ensure that the unit is set to one of these tones...

Page 11: ...rom the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Sounder power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2...

Page 12: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single alarm horn sounder For more information see manual D197 00 651 IS available from t...

Page 13: ...ion B pins 2 3 linked Places power supply terminal Fault resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 16 4 SIL 2 Hard Reset Function...

Page 14: ...o input D1xS1FDC024 S D1xS1RDC024 S Failure to Sound Integrity in respect of failure to release SIL 2 Total Failure rate 0 447 pmh hazardous failure rate revealed 0 443 pmh hazardous failure rate unre...

Page 15: ...g The values of resistors available are shown in table 7 below Code Resistor Value Default resistor coding as follows D1xS1FDC024AB1S1R AFZ Example of a custom requirement resistor coding D1xS1FDC024A...

Page 16: ...0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1...

Page 17: ...OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve EOL EOL S2 EOL S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT...

Page 18: ...S NTS SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED Stage 2 ve Common ve IN Common ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 OF 2 2 EOL S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUP...

Page 19: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Page 20: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 21: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Page 22: ...te and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on th...

Reviews: