Sheet 6 of 8

 

 

9.3 

Tone Selection 

 

The  D1x  Alarm  Horn  Sounders  have  64  different  tones  that  can  be 
selected  independently  for  the  first  and  second  stage  alarms.  The 
tones are selected by operation of the tone setting DIP switch 1 & DIP 
2witch 2 (see fig 8) on the PCB, for stage 1 and stage 2 respectively.  
 

Default = Switch 2   

S2 - Tone 1 

0 0 0 0 0 0 

Default = Switch 1  

S1 

– Tone 44 

1 1 0 1 0 1 

 

 

(ON = 1, OFF = 0) 

Figure 8: DIP switch configuration 

 
 
 

The sounder can also be switched to sound the third and fourth stage 
alarm tones.

 

 

The tone table (D221-95-001-IS) shows the switch positions for the 64 
tones on first and second stages and which tones are available for the 
third and fourth stages dependent on the Stage 1 DIP switch setting. 
 
Following  table  (Table  3)  is  a  summary  of  DC:  D190-06-001;  AC: 
D190-06-005 wiring options.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Config. 

Voltage 

Configuration Description 

Features  

Product 
Option 
Identifier 

1a 

DC 

Single Stage Configuration 

 

Line monitoring 

 

Positive Switching 

1b 

DC 

Two Stage Configuration 

 

Common Negative  

 

Positive Switching 

1c 

DC 

Three/Four Stage Configuration 

 

Common Negative  

 

Positive Switching 

DC 

Three/Four Stages. Voltage Free 2nd, 3rd & 
4th Stage Activation Configuration 

 

Common Positive 

 

Customer  Set  H1  &  H2  to  Negative 
Switching  

DC 

Two Stage Configuration 

 

Independent Stage Input 

 

Reverse Polarity Stage Monitoring 

DC 

Two Stage Configuration 

 

Line Stage Monitoring (Use suitable 
monitoring relays/ modules) 

 

Not to be used in reverse polarity 
monitoring 

DC 

Two/Three Stage Voltage Free Activation 
Configuration 

 

DC 

Three/Four Stage Configuration 

 

Independent Stage Input 

 

Line Stage Monitoring (Use suitable 
monitoring relays/ modules) 

 

Positive Switching (Default) 

1a 

AC 

Single Stage Configuration 

 

1b 

AC 

Three/Four Stage Configuration 

 

AC 

Two/Three Stage Voltage Free Activation 
Configuration 

 

Table  3:  Summary  of  Wiring  Options.  See  Document  D190-06-001  for  DC  Schematic  Diagrams;  D190-06-005  for  AC  Schematic 
Diagrams. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for D1xS1 Series

Page 1: ...EEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPEN...

Page 2: ...o 75 C Ex db IIC T6 Gb Ta 55 C to 70 C Ex tb IIIC T82 C Db Ta 55 C to 75 C See Product table for electrical ratings of each unit model Certificate No DEMKO 19ATEX2141X IECEx ULD 19 0008X UKEx UL UL21U...

Page 3: ...ected to external conditions that might cause a build up of electrostatic charges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation se...

Page 4: ...and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm...

Page 5: ...n Sounders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for...

Page 6: ...iring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Neg...

Page 7: ...f Line Monitoring An optional 12 way terminal module is available to enable up to four alarm stages to be activated from three DC voltage output channels The three alarm stage activation inputs can be...

Page 8: ...Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly...

Page 9: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 10: ...US 100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Ton...

Page 11: ...al Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A...

Page 12: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 13: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Page 14: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Page 15: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Page 16: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Page 17: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 18: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Page 19: ...ate and Place of Issue London 24 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 20: ...Page left Intentionally blank...

Reviews: