Table 1: Tone selection table 
 

 

 

 

 

Switch 

Stage 2 

Stage 3 

Stage 4 

Stage 1 

Frequency Description 

 

(S2) 

(S3) 

(S4) 

Tone 1 

340 Hz Continuous 

   

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 2 

800/1000Hz @ 0.25 sec Alternating 

 

 

 

 

 

 

 

Tone 17 

Tone 5 

Tone 29 

Tone 3 

500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 4 

800/1000Hz @ 1Hz Sweeping 

 

 

 

 

 

 

 

Tone 6 

Tone 5 

Tone 29 

Tone 5 

2400Hz Continuous 

  

 

 

 

 

 

Tone 3 

Tone 20 

Tone 29 

Tone 6 

2400/2900Hz @ 7Hz Sweeping 

 

 

 

 

 

 

 

Tone 7 

Tone 5 

Tone 29 

Tone 7 

2400/2900Hz @ 1Hz Sweeping 

 

 

 

 

 

 

 

Tone 10 

Tone 5 

Tone 29 

Tone 8 

500/1200/500Hz @ 0.3Hz Sweeping 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 9 

1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P. 

 

 

 

 

 

 

 

Tone 15 

Tone 2 

Tone 29 

Tone 10  2400/2900Hz @ 2Hz Alternating 

 

 

 

 

 

 

 

Tone 7 

Tone 5 

Tone 29 

Tone 11  1000Hz @ 1Hz Intermittent 

   

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 12  800/1000Hz @ 0.875Hz Alternating 

 

 

 

 

 

 

 

Tone 4 

Tone 5 

Tone 29 

Tone 13  2400Hz @ 1Hz Intermittent 

   

 

 

 

 

 

Tone 15 

Tone 5 

Tone 29 

Tone 14  800Hz 0.25sec on, 1 sec off Intermittent 

   

 

 

 

 

 

Tone 4 

Tone 5 

Tone 29 

Tone 15  800Hz Continuous 

  

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 16  660Hz 150mS on, 150mS off Intermittent 

   

 

 

 

 

 

Tone 18 

Tone 5 

Tone 29 

Tone 17  544Hz (100mS)/440Hz (400mS) - NF S 32-001 

 

 

 

 

 

 

 

Tone 2 

Tone 27 

Tone 29 

Tone 18  660Hz 1.8sec on, 1.8sec off Intermittent 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 19  1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s -NFC48-265 

   

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 20  660Hz Continuous 

  

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 21  554Hz/440Hz @ 1Hz Alternating 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 22  544Hz @ 0.875 sec. Intermittent 

   

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 23  800Hz @ 2Hz Intermittent 

   

 

 

 

 

 

Tone 6 

Tone 5 

Tone 29 

Tone 24  800/1000Hz @ 50Hz Sweeping 

 

 

 

 

 

 

 

Tone 29 

Tone 5 

Tone 29 

Tone 25  2400/2900Hz @ 50Hz Sweeping 

 

 

 

 

 

 

 

Tone 29 

Tone 5 

Tone 29 

Tone 26  Bell 

 

 

 

 

 

 

 

Tone 2 

Tone 15 

Tone 29 

Tone 27  554Hz Continuous 

  

 

 

 

 

 

Tone 26 

Tone 5 

Tone 29 

Tone 28  440Hz Continuous 

  

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 29  800/1000Hz @ 7Hz Sweeping 

 

 

 

 

 

 

 

Tone 7 

Tone 5 

Tone 29 

Tone 30  300Hz Continuous 

  

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 31  660/1200Hz @ 1Hz Sweeping 

 

 

 

 

 

 

 

Tone 26 

Tone 5 

Tone 29 

Tone 32  Two tone chime. 

 

 

 

 

 

 

 

Tone 26 

Tone 15 

Tone 29 

Tone 33  745Hz @ 1Hz Intermittent 

   

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 34  1000 & 2000Hz @ 0.5 sec Alternating - Singapore 

 

 

 

 

 

 

 

Tone 38 

Tone 45 

Tone 29 

Tone 35  420Hz @ 0.625 sec Australian Alert 

   

 

 

 

 

 

Tone 36 

Tone 5 

Tone 29 

Tone 36  500-1200Hz 3.75sec /0.25sec. Australian Evac. 

 

 

 

 

 

 

 

Tone 35 

Tone 5 

Tone 29 

Tone 37  1000Hz Continuous - PFEER Toxic Gas 

  

 

 

 

 

 

Tone 9 

Tone 45 

Tone 29 

Tone 38  2000Hz Continuous 

  

 

 

 

 

 

Tone 34 

Tone 45 

Tone 29 

Tone 39  800Hz 0.25sec on, 1 sec off Intermittent 

   

 

 

 

 

 

Tone 23 

Tone 17 

Tone 29 

Tone 40  544Hz (100mS)/440Hz (400mS) - NF S 32-001 

 

 

 

 

 

 

 

Tone 31 

Tone 27 

Tone 29 

Tone 41  Motor Siren - slow rise to 1200 Hz 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 42  Motor Siren - slow rise to 800 Hz 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 43  1200 Hz Continuous 

  

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 44  Motor Siren - slow rise to 2400 Hz 

 

 

 

 

 

 

 

Tone 2 

Tone 5 

Tone 29 

Tone 45  1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm 

   

 

 

 

 

 

Tone 38 

Tone 34 

Tone 29 

 

Summary of Contents for D105AX

Page 1: ...Steady o 2Hz flash rate 2 Operating and Marking All units have the following operating requirements and limitations Sounder only outputs Unit Type No Voltage Range Current D105AX 24Vdc 10 30Vdc 256mA...

Page 2: ...nnector the unit will need to be supplied with power DC units can be powered when completing recording and set up See section 7 Appello Setup Guide overleaf for Set up instructions and functions 6 Ton...

Page 3: ...llo unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or...

Page 4: ...tch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Playback Message only Play...

Page 5: ...ons 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Switch on power or Press re...

Page 6: ...B 16 11 22 Sheet 6 of 9 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stag...

Page 7: ...0 051 IS_Issue_B 16 11 22 Sheet 7 of 9 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper J4 ME to ON position centre and right pin connected 3 Switch on power o...

Page 8: ...umper J5 S M on Master unit to master position on Set jumper J5 S M on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Master unit fir...

Page 9: ...e 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 se...

Reviews: