E2S D1 B2LD2 Series Instruction Manual Download Page 2

 

E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D191-00-401-IS

 

Issue 3

 

28-11-22

Sheet 2 of 6

 

2.2 NEC Class / Zone ratings US 

 
The D1xB2LD2 LED beacons comply with the following 
standards: 

 

UL 60079-0-2013 
UL 60079-1-2015 
UL 60079-31-2015 
 

The D1xB2LD2 LED Beacon is rated as follows: 
 

Class I Zone 1 AEx db IIC T5 Ta -55°C to +80°C 
Class I Zone 1 AEx db IIC T6 Ta -55°C to +70°C 
Zone 21 AEx tb IIIC T100°C Ta -55°C to +80°C 

 

Installation must be carried out in compliance with the 
National Electric Code. 

 
2.3 CEC Class / Zone ratings Canada 
 

The D1xB2LD2 LED beacons comply with the following 
standards: 

CAN/CSA C22.2 No. 60079-0-2015 
CAN/CSA C22.2 No. 60079-1-2016 
CAN/CSA C22.2 No. 60079-31-2015 

 

The D1xB2LD2 LED Beacon is rated as follows: 

Ex db IIC T5 Ta -55°C to +80°C 
Ex db IIC T6 Ta -55°C to +70°C 
Ex tb IIIC T100°C Ta -55°C to +80°C 

 

Installation must be carried out in compliance with the 
Canadian Electric Code 
 

2.4 ATEX / IECEx & UKEx Certification 

 
The D1xB2LD2 LED beacons comply with the following 
standards: 

 
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7) 
EN60079-1:2010 / IEC60079-1: ed. 7.0 (2014-06) 
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11) 

 

The D1xB2LD2 LED Beacon is rated as follows: 
 

Ex db IIC T5 Gb Ta -55°C to +80°C 
Ex db IIC T6 Gb Ta -55°C to +70°C 
Ex tb IIIC T100°C Db Ta -55°C to +80°C 

 
For D1xB2LD2AC230 units, the certification approval has 
validated continuous use up to 38°C ambient and are for 
transient use up to 80°C ambient 

 

   

Certificate No. 

DEMKO 19 ATEX 2009X 
IECEx ULD 19.0006X 
UL21UKEX2130X 

ATEX Mark, 
Equipment Group and 
Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

 

2813 

UKCA Marking and 
Notified Body No.

 

 

0518

 

 
 
 
 

The units can be installed in locations with the following 
conditions: 
 

Area Classification Gas: 

 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist 
for a short time. 

 

Gas Groupings: 
 

Group IIA

Propane

Group IIB

Ethylene

Group IIC

Hydrogen and Acetylene 

 

Temperature Classification: 
 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

T5 

100ºC  

T6 

85ºC  (up to 70°C ambient) 

 

Dust Groupings: 
 

Group IIIA

Combustible Flyings 

Group IIIB

Non-conductive Dust 

Group IIIC

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

 

 

100ºC 

 

 

Equipment Category: 

2G / 2D  

 

Equipment Protection Level: 

Gb, Gc, Db, Dc  

 
Ambient Temperature Range: 

-55°C to +80°C 

 

2.5 Ingress Protection Ratings 

 
The product is rated for ingress Protection as follows: 
 
 

IP rating

 

per EN60529: 

IP66 

 

Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13 

 
Suitable for exposure to Acetone , Ammonium Hydroxide , 
Diethyl Ether , Ethyl Acetate , Ethylene Dichloride , Furfural, 
n-hexane , Methyl Ethyl Ketone , Methanol , 2-NitroPropane 
and Toluene. 
 
To  maintain  the  ingress  protection  rating,  the  cable  entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 

 
 
 
 
 
 
 

Summary of Contents for D1 B2LD2 Series

Page 1: ...R UNIQUEMENT AVEC UN CHIFFON HUMIDE NE PAS PEINTURER POUR R DUIRE LE RISQUE D INFLAMMATION DES ATMOSPH RES DANGEREUSES LE PREMIER CONDUIT DE CONDUIT DOIVENT AVOIR UN RACCORD D TANCH IT RACCORD MOINS D...

Page 2: ...units the certification approval has validated continuous use up to 38 C ambient and are for transient use up to 80 C ambient Certificate No DEMKO 19 ATEX 2009X IECEx ULD 19 0006X UL21UKEX2130X ATEX M...

Page 3: ...sification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres The installation of the units must also be in accordan...

Page 4: ...s or blanking plugs For use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained For use in explosive gas atmospheres a minimum ingress protection rating of IP5...

Page 5: ...000001 Steady Low Power Flashing 1Hz Flashing Triple Strike 100000 Flashing 1Hz Flashing Double Strike Flashing Triple Strike 101000 Flashing 1 5Hz Flashing 2Hz Flashing Double Strike 010000 Flashing...

Page 6: ...h the new lens cover Fig 10 Replacement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fi...

Page 7: ...Page left Intentionally blank...

Page 8: ...AR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT...

Page 9: ...Page left Intentionally blank...

Page 10: ...Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility...

Page 11: ...Ex d IIC T6 T3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic...

Page 12: ...Page left Intentionally blank...

Reviews: