E2S BExBG10D-P-SIL Instruction Manual Download Page 7

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. D197-00-112-IS        Issue B        16-06-17                         Sheet 7 of 17                                                                                          (7)

 

Multiple Unit Configuration

  

When multiple units are used in the system, the following considerations are to be made by the customer: 

 

1.  Customer panel capabilities -  

The customer is required to identify the minimum change in current the panel can detect (Panel resolution). This will 
therefore determine what resistors values to pick in section 3 below.  
 

2.  Topology -  

The customer has a number of options on how to set up the system.  

 

A single unit topology is where only one unit is connected to the customer interface line, as shown in figure 6. 
 

 

A series topology is where each unit is connected to one another as shown in figure 14. 
 

 

A star topology is where each unit is connected to a central source as shown in figure 15. 
 

3.  Resistor 

– TB1 Current Sense Resistor (default 3.3kΩ)   

The customer is required to calculate the total resistance of the system, to determine the change in current when a 
fault occurs

. The default customer sense resistor value is 3.3kΩ. Examples of calculations of resistance for steady 

mode and fault mode are shown in table 1.  
 

Panel 

Resolution 

Topology 

Resistor: 

TB1 CSR 

No. of 

Units 

Steady Mode: 

Active/Monitoring 

Fault Mode 

1 unit fault 

All units fault 

2mA 

Series 

3.3kΩ 

3 x 3.3kΩ = 9.9kΩ

 

 

0mA  

If one unit fails the 

whole system fails 

 

7mA 

Star 

3.3kΩ 

(3.3kΩ 

~ 7.3mA) 

3 x 7.3mA = 21.9mA 

(Fault unit): 

1 x 0mA = 0mA 

(Normal): 

2 x 7.3mA = 14.6mA 

(Fault unit): 

3 x 0mA = 0mA 

1.5mA 

Series 

3.3kΩ 

4 x 3.3kΩ = 13.2kΩ

 

 

0mA  

If one unit fails the 

whole system fails 

 

7mA 

Star 

3.3kΩ 

(3.3kΩ 

~ 7.3mA) 

4 x 7.3mA = 29.2mA 

(Fault unit): 

1 x 0mA = 0mA 

(Normal): 

3 x 7.3mA = 21.9mA 

(Fault unit): 

4 x 0mA = 0mA 

Table 1  
 
Note: - Cable fault 

  Between  the  panel  and  the  first  unit,  a  cable  short,  increases  the  current  (presenting  a  short  circuit  to  the  panel),  and  a 

cable cut/open reduces current (presenting an open circuit to the panel).  

  In series topology a cable short between units will short out one of the current sense resistors which results in an increase 

in the current used by the unit, and a cable cut/open reduces current (presenting an open circuit to the panel). 

  In star topology a cable short between units will short circuit the SIL 2 monitoring line hence presenting a short circuit to the 

panel,  an  open  circuit  fault  on  one  of  the  units  will  effectively  remove  one  of  the  current  sense  resistors  reducing  total 
effective resistance hence decreasing the total current seen by the panel.   

Summary of Contents for BExBG10D-P-SIL

Page 1: ...EX2006X IECEx KEM 10 0002X The BExBG10D and BExBG15D beacons have been certified for use in locations with the following conditions Area Classification Gas Zone 1 Explosive gas atmosphere likely to oc...

Page 2: ...location of the beacons should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the unit SAFETY WAR...

Page 3: ...or use in explosive dust atmospheres a minimum ingress protection rating of IP6X must be maintained The BEx beacon range can be supplied with the following types of adapters M20 to NPT M20 to NPT M20...

Page 4: ...the control panel A fault condition can be communicated via independent fault contacts or by the introduction to the monitoring circuit of an end of line resistor A SIL 2 system wiring for fault dete...

Page 5: ...re and may not be functioning correctly 13 2 Power Failure SIL 2 Failure SIL 2 Controller failure Internal function and system checking flags fault Rapid Power cycling System indicates power instabili...

Page 6: ...be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes As factory default when there is no fault the TB1 terminals 1 2 will be closed putting a 3 3k current...

Page 7: ...he default customer sense resistor value is 3 3k Examples of calculations of resistance for steady mode and fault mode are shown in table 1 Panel Resolution Topology Resistor TB1 CSR No of Units Stead...

Page 8: ...units default position is A Figure 7 Schematic of SIL 2 system wiring for fault detection in standby mode only 2 wire installation To evaluate the total current drawn from the SIL 2 unit use the equa...

Page 9: ...e customer can select a system EOL resistor The default fault resistor value is 2 2k which is recommended and is fitted according to the configuration topology chosen Panel Resolution Topology Resisto...

Page 10: ...et 10 of 17 10 14 3 Header Pins Settings Figure 8 J1 Header settings Figure 9 J2 Header settings J1 Header Pin Postion A Factory default position pins 1 2 not linked places TB1 Current sense resistor...

Page 11: ...i e the two header pins are not shorted together see Figure 5 18 Flip Flop Operation Two beacons can be mounted close to each other to form a flip flop operation where the beacons will flash alternat...

Page 12: ...Coding for Fault Resistor and Customer EOL Resistor The customer is able to identify the resistor values chosen on purchase from the product code This is represented by the last two characters BEXBG1...

Page 13: ...n in figure 12 Fig 13 Cover and Guard Fixtures 23 Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accorda...

Page 14: ...Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No D197 00 112 IS Issue B 16 06 17 Sheet 14 of 17...

Page 15: ...Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No D197 00 112 IS Issue B 16 06 17 Sheet 15 of 17 1...

Page 16: ...Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No D197 00 112 IS Issue B 16 06 17 Sheet 16 of 17...

Page 17: ...Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No D197 00 112 IS Issue B 16 06 17 Sheet 17 of 17 1...

Page 18: ...2011 Directive 2011 65 EU Restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS The product and all the components contained within it are in accordance wi...

Reviews: