E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D218-00-001-IS Issue 1 10/05/2021
INSTRUCTION & SERVICE MANUAL
A100 AlertAlarm Sounder
•
All models are approved for use as Audible Signal Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205-17
•
Type 3R / 13, (IP66 independently tested to EN60529:1991)
•
-
40°C to +66°C / -40°C to +151°F
General Signaling Canada:
A100DC024: -40°C to +55°C / -40°F to +131°F
A100AC230: -40°C to +40°C / -40°F to +104°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings.
Model
Nominal Voltage
Voltage Range
Nominal Operating Current
#
Max Operating RMS*
A100DC024
12V dc
10 - 60V ac
17mA
125mA
24V dc
33.5mA
48V dc
113mA
24 - 260V ac 50/60Hz /
60-260V dc
42.5mA
A100AC230
48V ac
42mA
115V ac
25mA
230V ac
17mA
*Max Operating current for worst-case input voltage;
#
Nominal current at nominal voltage and Tone 12