background image

 

 

 

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH    [email protected]        e2s.com                                            D218-00-001-IS Issue 1 10/05/2021  

 

Construction Product Regulation 

• 

A100DC024 is compliant to EN54-3:2001+A1+A2 

• 

Alarm devices – Sounder for use in fire detection and fire alarm systems installed in and around buildings  

• 

Type 3R / 13, IP66, Independently tested to EN60529:1991, (IP33C Compliant to EN54-3) 

• 

Type B Product, For Indoor & Outdoor use 

• 

Observe Precautions for handling electrostatic devices 

• 

-

25°C to +55°C compliant to EN54-3 

• 

Cable Glands must be suitably sealed and meet minimum IP33 for EN54-3 applications 

• 

Storage Temperature: -40°C to +70°C 

• 

Maintenance – None 

• 

Mounting - Units can be mounted using the 2-off ø6mm holes in the mounting lugs or through the back of 
the housing using the supplied gasket seal. 

2821 

S36282 

 

 

Approved Tones for EN54-3 Applications: 

 

•(Alternating Tone) 800/1000Hz @ 2Hz Alternating Tone 44 

•(Rising Tone) 500/1200Hz @ 0.26Hz (3.3s on, 0.5s off) Tone 8 

•(Fainting Tone) 1200/500Hz @ 1Hz Tone 2 

•(Continuous Tone) 800Hz Tone 21 

•(Pulsed Tone) 660Hz (150mS on, 150mS off) Tone 31 

•(Alternating Tone) 544Hz(100mS)/440Hz (400mS) Tone 5 

 

 

21 

Order Code: A100DC024 

Voltage Range: 18-60Vdc 

Nominal Voltage: 24Vdc / 48Vdc 

Max Current: 125mA @ 60Vdc  

DP-2821-CPR-0107 

A100DC024 @ 1m 

 

Horizontal Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Horizontal Sound Output 

Min Voltage (18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

98 

99.9 

99 

95.7 

94.8 

95.4 

94.7 

96.8 

95.9 

93 

91.9 

92.7 

45° 

97.8 

100.1 

99 

97.6 

94.7 

96.6 

95 

97 

96 

94.8 

92.1 

94 

75° 

101.5 

102.9 

102.4 

101.4 

98.3 

100.4 

98.7 

100.2 

99.5 

98.8 

94.9 

97.9 

105° 

101.4 

102.8 

102.5 

101.4 

98.1 

100.4 

98.6 

100.2 

99.5 

98.8 

94.9 

97.9 

135° 

97.4 

100 

98.9 

97.2 

94.9 

96.4 

94.6 

96.9 

95.9 

94.5 

92.2 

93.8 

165° 

97.5 

99.6 

98.9 

95.8 

94.7 

95.4 

94.3 

96.4 

95.8 

93 

91.8 

92.8 

 

Vertical Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Vertical Sound Output Min Voltage 

(18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

96.3 

99.8 

99 

95.5 

94.1 

95.3 

93.1 

96.7 

96 

92.8 

91.2 

92.6 

45° 

97.6 

99.9 

98.8 

97.4 

94.5 

96.3 

94.8 

96.8 

95.7 

94.6 

91.9 

93.8 

75° 

101.3 

103 

102.5 

101.4 

98.1 

100.5 

98.5 

100.1 

99.5 

98.7 

95 

97.8 

105° 

101.3 

102.8 

102.4 

101.3 

98.2 

100.5 

98.5 

100.1 

99.5 

98.7 

95 

97.7 

135° 

97.4 

99.9 

98.8 

97.6 

94.5 

96.3 

94.6 

96.8 

95.8 

94.8 

91.9 

93.7 

165° 

96.7 

100 

99 

95.5 

93.9 

95.4 

93.6 

96.9 

96 

92.7 

91.1 

92.7 

Summary of Contents for A100 AlertAlarm

Page 1: ...Elektriker gem den neuesten Vorschriften und Bestimmungen durchgef hrt werden Attenzione L installazione deve essere eseguita da un elettricista in conformit con i codici e le normative pi recenti At...

Page 2: ...se Mansell Road Acton London W3 7QH sales e2s com e2s com D218 00 001 IS Issue 1 10 05 2021 See D218 06 001 S2 S3 S2 S1 S2 S1 E E S3 S2 N L Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 AC DC See D2...

Page 3: ...als Impress House Mansell Road Acton London W3 7QH sales e2s com e2s com D218 00 001 IS Issue 1 10 05 2021 INSTRUCTION SERVICE MANUAL A100 AlertAlarm Sounder 2x 1Nm 20mm 98 3 86in 60 3 2 37in 35 9 1 4...

Page 4: ...5 21 Order Code A100DC024 Voltage Range 18 60Vdc Nominal Voltage 24Vdc 48Vdc Max Current 125mA 60Vdc DP 2821 CPR 0107 A100DC024 1m Horizontal Sound Output Max Voltage 60 Vdc LAFmax T dB A Horizontal S...

Page 5: ...be fitted with suitably rated cable glands or stopping plugs EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet th...

Page 6: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 7: ...ge Initial Peak Initial RMS A100DC024 24V dc 10 60V dc 298mA 56 4mA A100DC024 Sounder Directional Characteristics for Canadian Fire CAN ULC S525 at 10 feet Horizontal Axis Vertical Axis Angle OSPL Ang...

Page 8: ...A105N D105 DC SOUNDER WIRING DIAGRAMS INTRODUCTION NTS 1 1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K M...

Page 9: ...E A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 005 R S RAIT B ISARD R N POTTS OF A100 A105N D105 AC WIRING DIAGRAMS NTS...

Page 10: ...Page left Intentionally blank...

Page 11: ...Page left Intentionally blank...

Page 12: ...Page left Intentionally blank...

Reviews: