External earthing connections should be made to the M4 
earth  stud,  using  a  ring  crimp  terminal  to  secure  the 
earth  conductor  to  the  earth  stud.  The  external  earth 
conductor should be at least 4mm2 in size. 

 

7.3. Cable Glands, Blanking Elements & Adapters 

 
Follow the minimum temperature ratings of cables and cable 
glands according to the approvals applied. 
 

ATEX / IECEx & UKEx Requirements 
 
For  high  ambient  temperatures  the  cable  entry 
temperature  may  exceed  70ºC  or  the  cable  branching 
point  temperature  may  exceed  80ºC  and  therefore 
suitable heat resisting cables and cable glands must be 
used,  with  a  rated  service  temperature  at  least  as 
stated below: 
 

 

Table 2: ATEX / IECEx & UKEx Min. Ratings of Cables & 

Cable Glands. 

 
NEC / CEC Requirements Only 
 
For  high  ambient  temperatures  the  cable  entry 
temperature  may  exceed  60ºC  or  the  cable  branching 
point  temperature  may  exceed  60ºC  and  therefore 
suitable heat resisting cables and cable glands must be 
used,  with  a  rated  service  temperature  at  least  as 
stated below: 
 

 

Table 3: NEC / CEC Min. Ratings of Cables & Cable Glands. 

 

Cable Glands & Blanking Plugs 

 
Appropriate cable glands to be customer supplied. 
 

ATEX / IECEx & UKEx Requirements Only 

 

The  cable  gland  entries  have  an  M20  x  1.5  entry 
thread. Only suitably rated and ATEX / IECEx & UKEx 
certified  cable  glands  which  must  be  suitable  for  the 
type  of  cable  being  used  and  also  meet  the 
requirements of the current Ex ‘d’ flameproof installation 
standards EN 60079-14 / IEC60079-14. 
 
If the installation is made using conduit, openings must 
have a sealing fitting connected as close as practical to 
the wall of the enclosure, but in no case more than the 
size of the conduit or 50mm, whichever is the lesser. 
 
When  only  one  cable  entry  is  used  the  other  entries 
must be closed with suitably rated and ATEX / IECEx & 
UKEx certified blanking plugs. 

 
 
 
 

NEC / CEC Requirements Only 
 
The cable entries have an M20 x 1.5 – 6H entry thread. 
If  the  installation  is  made  using  cable  glands,  only 
suitably rated and certified cable glands must be used. 
They must be suitable for the type of cable being used 
and  also  meet  the  requirements  of  the  current  NEC  / 
CEC installation standards. 
 
If the installation is made using conduit, openings must 
have a sealing fitting connected as close as practical to 
the wall of the enclosure, but in no case more than the 
size of the conduit or 50mm, whichever is the lesser. 
 
For  use  in  Class  I  Division  II  locations,  in  order  to 
maintain  the  db  type  protection,  flameproof  conduit 
seals and/or cable glands must be used. 
 
Any unused cable entries must be closed with suitably 
rated and certified blanking plugs. 

 

Ingress Protection 

 
Follow instructions according to the approvals applied. 
 

ATEX / IECEx & UKEx Requirements Only 
 
If a high IP (Ingress Protection) rating is required then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 
 
NEC / CEC Requirements Only 
 
If a high IP (Ingress Protection) rating is required then a 
suitable  sealing  washer  must  be  fitted  under  the  cable 
glands or blanking plugs. A minimum ingress protection 
rating  of  IP6X  must  be  maintained  for  installations  in 
explosive dust atmospheres. 

 

Adapters 

 
The GNEx Beacon Range can be supplied with the following 
types of adapters: 
 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 
It  is  important  to  note  that  stopping  plugs  cannot  be  fitted 
onto adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated as per the 
applicable standards. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for GNExB2LD2 Series

Page 1: ...ermissible Nominal current at nominal voltage and 1Hz flash rate Max rated current at worst case supply voltage and flash rate Table 1 Electrical Ratings Ensure the system power supply is capable of providing the maximum current required for all beacons Review associated cable size length and quantity of beacons on each circuit 2 Warnings POTENTIAL ELECTROSTATIC CHARGING HAZARD CLEAN ONLY WITH A D...

Page 2: ...gs Canada Codes Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 No 60079 1 Ed 3 2016 Electrical Apparatus for Explosive Gas Atmospheres Part 1 Flameproof Enclosures d Ratings GNExB2 LD2DC024 LD2AC115 LD2AC230 Ex db IIC T5 Gb Ta 50 C to 70 C Ex db IIC T6 Gb Ta 50 C to 65 C Installation must be carried out in compliance with t...

Page 3: ...xternal conditions that might cause a build up of electrostatic charges on non conducting surfaces The stainless steel beacon guard is not earthed and may generate an ignition capable level of electrostatic charges It has a capacitance of 10pF according to EN IEC60079 0 clause 7 5 6 Product Mounting and Access 6 1 Location and Mounting The location of the beacons should be made with due regard to ...

Page 4: ...rom power source before installation or service to prevent electric shock Débranchez le de la source d alimentation avant l installation ou l entretien pour éviter tout choc électrique The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training 7 2 Cable Selection and C...

Page 5: ... enclosure but in no case more than the size of the conduit or 50mm whichever is the lesser When only one cable entry is used the other entries must be closed with suitably rated and ATEX IECEx UKEx certified blanking plugs NEC CEC Requirements Only The cable entries have an M20 x 1 5 6H entry thread If the installation is made using cable glands only suitably rated and certified cable glands must...

Page 6: ...hronised check that the DIP switch is set to1 Hz see Figure 6 9 End of Line Monitoring DC Units All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber If an end of line resistor is used it must have a minimum resistance value of 3k3 ohms and...

Page 7: ...rd Clean only with a damp cloth 12 SIL 2 Reliability Data Reliability and Functional safety IEC EN61508 which has been assessed and is considered suitable for use in low demand safety function 1 Random Hardware Failures and Architectural constraints route 2H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input by...

Page 8: ... DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D156 06 401 R N POTTS OF GNExB2 LD2 BEACON NTS 1 1 A FORMAT UPDATE MA 03 12 2021 B INTRODUCTION J S 14 11 19 GNExB2 LD2 R N POTTS J SPILLER 14 11 19 WIRING DIAG...

Page 9: ... B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applie...

Page 10: ...r Date and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of th...

Page 11: ...ke Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 ...

Page 12: ...er Date and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of...

Reviews: