CPC12EN bus controller
(
ControlPlex
®
)
2116
7
CPC12EN bus controller
(
ControlPlex
®
)
Notes
l
The CPC12 bus controller is only intended for use with safety
extra-low voltage (= 24 V DC).
l
Connection to a higher or not reliably disconnected voltage can
cause hazardous conditions or damages.
l
Only the intended circuit protectors must be used.
l
The technical data of the circuit protectors used have to be
observed.
l
The entire power distribution system must only be installed by
qualified personnel.
l
Only after expert installation must the device be supplied with
power.
l
After tripping of the circuit protector and before reset, the cause
of the failure (short circuit or overload) must be remedied.
l
The national standards (e.g. for Germany DIN VDE 0100) have
to be observed for installation and selection of feed and return
cables.
l
For convenient adjustment and configuration by means of
projecting software, a master data file (EDS file) will be made
available for downloading on the E-T-A homepage.
l
The CPC12 bus controller is not suitable for controlling safe-
ty-critical or functionally safe applications.
Please observe the separate user instruction manual for the CPC12
bus controller.
Safety Note
Caution:
Electrostatically sensitive sub-assemblies can
be destroyed by voltages far below the human
perception threshold. These voltages already occur
if you touch a component or electrical terminals of a
sub-assembly without being electrostatically discharged. The damage
of a sub -assembly caused by an overvoltage is often not immediately
recognised, but will be noticed only after a longer operating time.
All information and data given on our products are accurate and reliable to the best of our
knowledge, but E-T-A does not accept any responsibility for the use in applications which
are not in accordance with the present specification. E-T-A reserves the right to change
specifications at any time in the interest of improved design and performance. Dimensions
are subject to change without notice. Please enquire for the latest dimensional drawing with
tolerances if required. All dimensions, data, pictures and descriptions are for information
only and are not binding. Amendments, errors and omissions excepted. Part numbers of the
devices may differ from their marking.
EtherNet/IP-communication interface system
Overview of commands:
Writing/reading of device configuration (parameters)
l
Current limit value (50 % ... 100 %)
l
Rated current (1 A ... 10 A), writing of the rated current is only
possible with device type REX12D-TE and-REX22D-TE.
Reading of static product information
l
Product type
l
Serial number
l
Hardware version
l
Software version
Reading of dynamic product information / measuring values
l
Status CPC12
l
Internal cycle time
l
Error memory
l
Trip counter
l
Reason of last trip
l
Device status/ event
l
Load voltage: ACTUAL / MIN / MAX / MEDIUM VALUE
l
Load current: ACTUAL / MIN / MAX / MEDIUM VALUE
l
Supply voltage
l
Total current
Control commands
l
Switch on/off or reset load output
l
Reset trip counter
l
Set parameters to factory setting
Ordering information
Series
CPC12
ControlPlex
®
bus controller
Design: Field bus system
EN
EtherNet/IP (connection: 2 x RJ45 female connector)
Mounting method
T
Rail mounting
ELBus connections
1
1 connection (right)
product versions
001
Marking
CPC12 EN - T 1 - 001
Ordering example