CPC12EN bus controller 

(

ControlPlex

®

)

2116

  7

CPC12EN bus controller 

(

ControlPlex

®

)

Notes

l

   The CPC12 bus controller is only intended for use with safety 

extra-low voltage (= 24 V DC).

l

   Connection to a higher or not reliably disconnected voltage can 

cause hazardous conditions or damages.

 Only the intended circuit protectors must be used.

 The technical data of the circuit protectors used have to be 

observed.

 The entire power distribution system must only be installed by 

qualified personnel.

 Only after expert installation must the device be supplied with 

power.

 After tripping of the circuit protector and before reset, the cause 

of the failure (short circuit or overload) must be remedied.

 The national standards (e.g. for Germany DIN VDE 0100) have 

to be observed for installation and selection of feed and return 

cables.

l

   For convenient adjustment and configuration by means of 

projecting software, a master data file (EDS file) will be made 

available for downloading on the E-T-A homepage.

l

   The CPC12 bus controller is not suitable for controlling safe-

ty-critical or functionally safe applications.

Please observe the separate user instruction manual for the CPC12 

bus controller.

Safety Note

Caution:
Electrostatically sensitive sub-assemblies can 
be destroyed by voltages far below the human 
perception threshold. These voltages already occur 
if you touch a component or electrical terminals of a 

sub-assembly without being electrostatically discharged. The damage 
of a sub -assembly caused by an overvoltage is often not immediately 
recognised, but will be noticed only after a longer operating time.

All information and data given on our products are accurate and reliable to the best of our 
knowledge, but E-T-A does not accept any responsibility for the use in applications which 
are not in accordance with the present specification. E-T-A reserves the right to change 
specifications at any time in the interest of improved design and performance. Dimensions 
are subject to change  without notice. Please enquire for the latest dimensional drawing with 
tolerances if required. All dimensions, data, pictures and descriptions are for information 
only and are not binding. Amendments, errors and omissions excepted. Part numbers of the 
devices may differ from their marking.

EtherNet/IP-communication interface system

Overview of commands:

Writing/reading of device configuration (parameters)

Current limit value (50 % ... 100 %) 

 

Rated current (1 A ... 10 A), writing of the rated current is only  
possible with device type REX12D-TE and-REX22D-TE.

Reading of static product information

Product type

Serial number

Hardware version

Software version

Reading of dynamic product information / measuring values

Status CPC12

Internal cycle time

Error memory

Trip counter

Reason of last trip

Device status/ event

Load voltage: ACTUAL / MIN / MAX / MEDIUM VALUE

Load current: ACTUAL / MIN / MAX / MEDIUM VALUE

Supply voltage

Total current

Control commands

Switch on/off or reset load output

Reset trip counter

Set parameters to factory setting

Ordering information

Series
CPC12

    

ControlPlex

®

 bus controller

 

Design: Field bus system

 EN

 EtherNet/IP (connection: 2 x RJ45 female connector)

 

  

Mounting method

 

   T 

Rail mounting 

 

  

 

ELBus connections 

 

 

  

   

 

1 connection (right)

 

     

  

product versions

 

     

   001 

Marking

CPC12 EN  -   T    1  -  001 

Ordering example

Summary of Contents for EtherNetIP ControlPlex CPC12EN

Page 1: ...ctronic intelligent circuit protectors of the REX system The CPC12 bus controller allows entire access on all required parameters of the intelligent circuit protectors their control unit and the visualisation of the device data This is provided at the field bus interfaces for the superordinate control unit and also at the third RJ45 interface for further connection Thus the system offers a fully p...

Page 2: ...current I0 typically 75 mA Supply via contact lever or additionally XD1 terminal 0 2 mm2 to 1 5 mm2 push in AWG24 AWG14 str Wire stripping length 8 mm EtherNet IP interface XF1 XF2 RJ45 Connection to Ethernet IP bus system When wiring and connecting to the Ethernet IP bus system the installation and wiring regulations of the EtherNet IP specification have to be observed Ethernet interface X1 RJ45 ...

Page 3: ...iced only after a longer operating time All information and data given on our products are accurate and reliable to the best of our knowledge but E T A does not accept any responsibility for the use in applications which are not in accordance with the present specification E T A reserves the right to change specifications at any time in the interest of improved design and performance Dimensions ar...

Page 4: ...tion Application example Terminal selection G E R M A N Y X1 Ethernet interface XF1 EtherNet IP interface XF2 EtherNet IP interface XD1 DC24V XD1 0V XD1 FE IP Reset LED LNK LED ACT LED LNK LED ACT LED LNK LED ACT XD1 Supply terminal LED US1 LED US2 LED NS LED MS Dimensions CPC12xx Tx xxx 80 23 7 5 98 5 92 Snap on socket for rail EN 60715 35x7 5 not included Ensure space for plugs and cables Label ...

Page 5: ...M12 T00 100 LINE DC24V 40A PM12 T01 00 GND DC24V 20A EM12 T00 000 GND DC24V 40A EM12 T00 300 GND DC24V 40A DC24V REX12D TA2 107 DC24V REX12D TA2 107 REX12D TA1 107 DC24V 10A 2A 2A 6A 6A PM12 T01 00 LOAD DC24V 20A M M 4 7 Schaltnetzteil Power supply PLC PLC To next control cabinet or to additional supply To next control cabinet or to additional supply ...

Page 6: ... upwards and remove connector arm can be closed Mount REX side by side with EM Remove REX from rail REX mount on symmetrical rail close connector arm CPC12 replacement or disassembly Unlatch with screwdriver Pull out at right angles to the rail Open connector arm Open connector arm Mounting or actuation of the connector arm must only be effected at dead voltage For start up the connector arm must ...

Page 7: ...2 T 0 V 13 14 Technical data Schematic diagram Please observe general data of REX EM PM Operating voltage UB DC 24 V 18 30 V Operating current IB Max 40 A Insulation coordination 0 8 kV pollution degree 2 Terminals LINE 1 Push in terminal PT 10 Wire stripping length 0 5 mm2 10 mm2 flexible AWG24 AWG8 rigid 18 mm Terminals 0 V Push in terminal PT 2 5 Wire stripping length 0 14 mm2 to 2 5 mm2 flexib...

Reviews: