background image

 www.e-t-a.de

2

CPC12EN bus controller 

(

ControlPlex

®

)

2116

  7

Technical data  (T

amb

 = 25 °C, U

B

 = V)

Visual signalling of RJ45 interfaces

LED LNK

Operating mode

Indication of operating mode

Link available

green

No link available

off

LED ACT

Operating mode

Indication of operating mode

Activity available

orange blinking

No activity

off

General data

Housing material

Plastic material

Mounting method

Symmetrical rail to EN 60715 - 35 x 7.5

Ambient temperature 

(TAMB)

-30 °C ...+ 60 °C  

(without condensation, cf. EN 60204-1)

Storage temperature

-40 °C … +70 °C

Mounting tempe5 °C … +60 °C

Damp heat

96 hrs / 95% RH RH/40 °C to IEC 60068-

2-78-Cab climate class 3K3 to EN 60721

Altitude

2,000 m above sea level 

3,000 m above sea level up to +55 °C 

4,000 m above sea level up to +50 °C

Operation pressure

4 bar above atmospheric pressure

Vibration resistance

5 g, test to IEC 60068-2-6 test Fc

Degree of protection

IP20

EMC requirements 

(EMC Directive, CE 

Logo)

Emitted interference:  EN 61000-6-3 

Noise immunity:      EN 61000-6-2

Insulation co- 
ordination (IEC 60664)

Overvoltage category II/  
pollution degree 3

Instructions for  

installation

Mounting or actuation of the REX  

connector arm must only be effected  

at dead-voltage. For start-up the REX  

connector arm must be closed.

Technical data  (T

amb

 = 25 °C, U

B

 = V)

Operating voltage U

B

DC 24 V (18 ... 30 V)

Reverse polarity  

protection

yes

Quiescent current I

0

typically 75 mA

Supply via contact lever or additionally
XD1 terminal 

0.2 mm

2

 to 1.5 mm

2

(push-in)

AWG24 – AWG14 str.

Wire stripping length

8 mm

EtherNet/IP interface (XF1, XF2)

RJ45

Connection to Ethernet/IP bus system. 

When wiring and connecting to the 

Ethernet IP bus system the installation 

and wiring regulations of the EtherNet/

IP™ specification have to be observed.

Ethernet interface (X1)

RJ45 

Communication interface to web server

IP reset

Momentary switch 

Reset IP address 

(interface X1) by pushing the  

momentary switch for min. 3 sec

Dimensions  

(H x W x D)

23 x 80 x 98.5 mm  

(tolerances to DIN ISO 286 part 1 IT13)

Mass

approx. 70 g

System components
EM12-T supply module               
Bus controller  
Circuit protectors can 

be mounted side-by-

side

Types
EM12-T00-000-DC24V-40A
CPC12xx-Tx-xxx
REX12D-T 
REX22D-T

Visual operation status indication  
by means of multicoloured LED

Operating mode

Indication of operating mode

LED US1

LED US2

Supply voltage OK

green

---

Firmware update

off

off

Actuator voltage OK

green

green

No actuator voltage

green

red

No device connected 

or bus error

green

orange blinking

Operating mode

Indication of operating mode

LED NS (network status)

No IP address

off

Valid IP address, no 
CIP connection

green blinking

Active CIP connection green

CIP connection time 
exceeded 

red blinking

Double IP address 

detected

red

Operating mode

Indication of operating mode

LED MS (module status)

Ready to communicate green

Internal configuration

green blinking

Critical error recoverable red blinking

Critical error not 

recoverable

red

Summary of Contents for EtherNetIP ControlPlex CPC12EN

Page 1: ...ctronic intelligent circuit protectors of the REX system The CPC12 bus controller allows entire access on all required parameters of the intelligent circuit protectors their control unit and the visualisation of the device data This is provided at the field bus interfaces for the superordinate control unit and also at the third RJ45 interface for further connection Thus the system offers a fully p...

Page 2: ...current I0 typically 75 mA Supply via contact lever or additionally XD1 terminal 0 2 mm2 to 1 5 mm2 push in AWG24 AWG14 str Wire stripping length 8 mm EtherNet IP interface XF1 XF2 RJ45 Connection to Ethernet IP bus system When wiring and connecting to the Ethernet IP bus system the installation and wiring regulations of the EtherNet IP specification have to be observed Ethernet interface X1 RJ45 ...

Page 3: ...iced only after a longer operating time All information and data given on our products are accurate and reliable to the best of our knowledge but E T A does not accept any responsibility for the use in applications which are not in accordance with the present specification E T A reserves the right to change specifications at any time in the interest of improved design and performance Dimensions ar...

Page 4: ...tion Application example Terminal selection G E R M A N Y X1 Ethernet interface XF1 EtherNet IP interface XF2 EtherNet IP interface XD1 DC24V XD1 0V XD1 FE IP Reset LED LNK LED ACT LED LNK LED ACT LED LNK LED ACT XD1 Supply terminal LED US1 LED US2 LED NS LED MS Dimensions CPC12xx Tx xxx 80 23 7 5 98 5 92 Snap on socket for rail EN 60715 35x7 5 not included Ensure space for plugs and cables Label ...

Page 5: ...M12 T00 100 LINE DC24V 40A PM12 T01 00 GND DC24V 20A EM12 T00 000 GND DC24V 40A EM12 T00 300 GND DC24V 40A DC24V REX12D TA2 107 DC24V REX12D TA2 107 REX12D TA1 107 DC24V 10A 2A 2A 6A 6A PM12 T01 00 LOAD DC24V 20A M M 4 7 Schaltnetzteil Power supply PLC PLC To next control cabinet or to additional supply To next control cabinet or to additional supply ...

Page 6: ... upwards and remove connector arm can be closed Mount REX side by side with EM Remove REX from rail REX mount on symmetrical rail close connector arm CPC12 replacement or disassembly Unlatch with screwdriver Pull out at right angles to the rail Open connector arm Open connector arm Mounting or actuation of the connector arm must only be effected at dead voltage For start up the connector arm must ...

Page 7: ...2 T 0 V 13 14 Technical data Schematic diagram Please observe general data of REX EM PM Operating voltage UB DC 24 V 18 30 V Operating current IB Max 40 A Insulation coordination 0 8 kV pollution degree 2 Terminals LINE 1 Push in terminal PT 10 Wire stripping length 0 5 mm2 10 mm2 flexible AWG24 AWG8 rigid 18 mm Terminals 0 V Push in terminal PT 2 5 Wire stripping length 0 14 mm2 to 2 5 mm2 flexib...

Reviews: