www.e-t-a.de
2
CPC12EN bus controller
(
ControlPlex
®
)
2116
7
Technical data (T
amb
= 25 °C, U
B
= V)
Visual signalling of RJ45 interfaces
LED LNK
Operating mode
Indication of operating mode
Link available
green
No link available
off
LED ACT
Operating mode
Indication of operating mode
Activity available
orange blinking
No activity
off
General data
Housing material
Plastic material
Mounting method
Symmetrical rail to EN 60715 - 35 x 7.5
Ambient temperature
(TAMB)
-30 °C ...+ 60 °C
(without condensation, cf. EN 60204-1)
Storage temperature
-40 °C … +70 °C
Mounting tempe5 °C … +60 °C
Damp heat
96 hrs / 95% RH RH/40 °C to IEC 60068-
2-78-Cab climate class 3K3 to EN 60721
Altitude
2,000 m above sea level
3,000 m above sea level up to +55 °C
4,000 m above sea level up to +50 °C
Operation pressure
4 bar above atmospheric pressure
Vibration resistance
5 g, test to IEC 60068-2-6 test Fc
Degree of protection
IP20
EMC requirements
(EMC Directive, CE
Logo)
Emitted interference: EN 61000-6-3
Noise immunity: EN 61000-6-2
Insulation co-
ordination (IEC 60664)
Overvoltage category II/
pollution degree 3
Instructions for
installation
Mounting or actuation of the REX
connector arm must only be effected
at dead-voltage. For start-up the REX
connector arm must be closed.
Technical data (T
amb
= 25 °C, U
B
= V)
Operating voltage U
B
DC 24 V (18 ... 30 V)
Reverse polarity
protection
yes
Quiescent current I
0
typically 75 mA
Supply via contact lever or additionally
XD1 terminal
0.2 mm
2
to 1.5 mm
2
(push-in)
AWG24 – AWG14 str.
Wire stripping length
8 mm
EtherNet/IP interface (XF1, XF2)
RJ45
Connection to Ethernet/IP bus system.
When wiring and connecting to the
Ethernet IP bus system the installation
and wiring regulations of the EtherNet/
IP™ specification have to be observed.
Ethernet interface (X1)
RJ45
Communication interface to web server
IP reset
Momentary switch
Reset IP address
(interface X1) by pushing the
momentary switch for min. 3 sec
Dimensions
(H x W x D)
23 x 80 x 98.5 mm
(tolerances to DIN ISO 286 part 1 IT13)
Mass
approx. 70 g
System components
EM12-T supply module
Bus controller
Circuit protectors can
be mounted side-by-
side
Types
EM12-T00-000-DC24V-40A
CPC12xx-Tx-xxx
REX12D-T
REX22D-T
Visual operation status indication
by means of multicoloured LED
Operating mode
Indication of operating mode
LED US1
LED US2
Supply voltage OK
green
---
Firmware update
off
off
Actuator voltage OK
green
green
No actuator voltage
green
red
No device connected
or bus error
green
orange blinking
Operating mode
Indication of operating mode
LED NS (network status)
No IP address
off
Valid IP address, no
CIP connection
green blinking
Active CIP connection green
CIP connection time
exceeded
red blinking
Double IP address
detected
red
Operating mode
Indication of operating mode
LED MS (module status)
Ready to communicate green
Internal configuration
green blinking
Critical error recoverable red blinking
Critical error not
recoverable
red