background image

 - 2 -

1 Description

Electronic circuit protector type ESX10-T is designed to ensure 

selective disconnection of DC 24 V load systems because it responds 

much faster to overload or short circuit conditions than the switch-mode 

power supply. This is achieved by active current limitation. The ESX10-T 

limits the highest possible current to 1.3 to 1.8 times the selected rated 

current of the circuit protector. Thus it is possible to switch on 

capacitive 

loads of up to 20,000 µF, but they are disconnected only in the event of an 

overload or short circuit.

For optimal alignment with the characteristics of the application the 

current rating of the ESX10-T can be selected in fixed values from 0.5 

A...12 A. Failure and status indication are provided by a multicolour LED 

and an integral short-circuit-proof status output or a potential-free signal 

contact. Remote operation is possible by means of a remote reset signal 

or a remote ON/OFF control signal. The manual ON/OFF button allows 

separate actuation of individual load circuits.

Upon detection of overload or short circuit in the load circuit, the 

MOSFET of the load output will be blocked to interrupt the 

current flow. The load circuit can be re-activated via the remote 

electronic reset input, control input or manually by means of the 

ON/OFF button.

2  Technical Data (Tambient = 25 °C, US = DC 24 V)

Operating data
Operating voltage U

S

DC 24 V (18...32 V) 

Current rating I

N

0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A

Closed current I

0

ON condition: typically 20...30 mA     

depending on signal output

Status indication 

by means of

l

 multicolour LED: 

   

Green:   

- unit is ON, power-MOSFET 

  is switched on

- status output SF ON, su DC 24 V 

Orange:  

- in the event of overload or short  

   

   circuit until electronic disconnection

Red:  

- unit electronically disconnected 

- load circuit/Power-MOSFET OFF

OFF:    

- manually switched off (S1 = OFF) or  

  device is dead

- undervoltage (U

< 8 V)

- after switch-on till the end of the delay  

   period 

 

 

l

 status output SF (option) 

l

 potential-free signal contact F (option)

   

 

l

 ON/OFF/ condition of switch S1

Load circuit
Load output

Power-MOSFET switching output

(high side switch)

Overload disconnection 

typically 1.1 x I

N

 (1.05...1.35 x I

N

)

Short-circuit current I

K

Active current limitation with  

I

Limit

 = typically 1.8/1.5/1.4/4.3 x I

N

,  

I

Limit

 depending on I

N

  

(typical I

Limit

 - values see table 1)

Trip characteristic

active current limitation (see table 1)

Trip thresholds/trip times 

(t

1

, t

2

) at overcurrent

1. threshold: 

at I

load

> typically 1.1 x I

N

...I

Limit

: (I

Limit

 see 

table 1) t

1

 = typically 3s. 

2. threshold: 

at I

load

 = I

Limit

t

2

 = typically 100 ms...3 s.

Temperature              

disconnection

internal temperature monitoring with  

electronic disconnection

Low voltage monitoring

load output

with hysteresis, no reset required

load “OFF” at U

S

 < 8 V

Starting delay t

start

typically 0.5 sec after every switch-on

and after applying U

S

Disconnection of load 

circuit

electronic disconnection

Free-wheeling circuit

external free-wheeling diode  

recommended with inductive load

Several load outputs must not be connected in parallel
Status output SF

ESX10-T.-114/-124/-127

Electrical data

plus-switching signal output, connects U

S

 

to terminal 12 of module 17plus nominal 

data: DC 24 V / max. 0.2 A (short circuit 

proof) status output is internally connected 

to GND with a 10 kOhm resistor

Status OUT

ESX10-TB-114/-124 (signal status OUT), 

at U

S

 = +24 V 

+24 V = S1 is ON, load output connected  

through 0V = S1 is ON, load output blocked  

and/or switch S1 is OFF

red LED lighted

Status OUT

ESX10-TB-127 (signal status OUT inverted), 

at U

B

 = + 24 V

+ 24 V = S1 is ON, load output locked 

red LED lighted

0 V = S1 is ON, load output connected and/

or switch S1 is OFF.

OFF condition

0 V level at status output when:

 

l

 

switch S1 is in ON position, but device is  

  still in switch-on delay

 

l

 

switch S1 is OFF, or control signal OFF,  

  device is switched off 

l

 no operating voltage  U

S

Signal output F

ESX10-T.-101/-102

Electrical data

potential-free signal contact  

max. DC 30 V/0.5 A, min. 10 V/10 mA

ON condition LED green

oltage U

S

 applied, switch S1 is in ON  

position no overload, no short circuit

OFF condition LED off

device switched off (switch S1 is in 

  OFF position) 

l

 

no voltage U

S

 applied

Fault condition LED orange overload condition > 1.1 x I

up to   

electronic disconnection

Fault condition LED red

electronic disconnection upon

overload or short circuit

ESX10-TB-101

single signal, make contact contact 

SC/SO-SI open

ESX10-TB-102

single signal, break contact

contact SC/SO-SI closed

Fault 

signal output fault conditions:

l

  

no operating voltage  U

S

 

l

  

ON/OFF switch S1 is in OFF position 

l

  

red LED lighted 

(electronic disconnection)

Reset input RE

ESX10-T.-124/-127

Electrical data

voltage: max.  + DC 32 V 

high 

> DC 8 V ≤ DC 32 V

low 

≤ DC 3 V > 0 V

power consumption typically 2.6 mA  

(+DC 24 V) 

min. pulse duration typically 10 ms

Reset signal RE 

terminal 22

The electronically blocked ESX10-

TB-124/-127 may remotely be reset via an 

external momentary switch due  to the fal-

ling edge of a +24 V pulse. A common reset 

signal can be applied to several devices 

simultaneously. Switched on devices remain 

unaffected.

Control input IN+

ESX10-T.-114

Electrical data

see reset input RE

Control signal IN+

terminal 21

+24V level (HIGH): device will be switched 

(terminal 21) on by a remote ON/OFF 

signal 0 V level (LOW): device will be 

switched off by a remote ON/OFF signal

Switch S1 ON/OFF

unit can only be switched on with S1 if a  

HIGH level is applied to IN+

LED display

ON: LED green / OFF: LED red

General data
Fail-safe element

backup fuse for ESX10-T not required  

because of the integral redundant fail-safe 

element

Terminals

LINE+/LOAD+/0V

screw terminals 

M4

max. cable cross section

rigid and flexible 

0,5 - 16 mm² 

flexible with wire end ferrule w/wo plastic sleeve 

0.5 - 10 mm

2

wire stripping length 

10 mm

tightening torque (EN 60934) 

1.5 - 1.8 Nm

multi-lead connection 

(2 identical cables)

rigid/flexible 

0.5 - 4 mm

2

flexible with wire end ferrule without plastic sleeve 

0.5 - 2,5 mm

2

flexible with TWIN wire end ferrule with plastic sleeve 0.5 - 6 mm

2

2  Technical Data (Tambient = 25 °C, US = DC 24 V)

Summary of Contents for ESX10-TA-DC 24 V

Page 1: ...P 54 is achieved after installation in a UV protected fully enclosed room control cabinet IEC EN60079 0 and IEC EN 60079 14 have be observed for installation Safety This device is not protected agains...

Page 2: ...rcuit external free wheeling diode recommended with inductive load Several load outputs must not be connected in parallel Status output SF ESX10 T 114 124 127 Electrical data plus switching signal out...

Page 3: ...ESX10 TB 6 A l Electronic current limitation ILimit occurs at typically 1 8 x IN which means that under all overload conditions independent of the power supply and the resistance of the load circuit t...

Page 4: ...0 TB 124 Load Load Load 22 1 LINE RE SF 23 22 1 LINE RE SF 23 22 1 LINE RE SF 23 Reset button 3 0V 3 0V 3 0V 24 V 0 V 0 5 A ESX10 TA 100 1 LINE 1 LINE 1 LINE 1 LINE 2 LOAD 2 LOAD 2 LOAD 2 LOAD 3 0V 3...

Page 5: ...or jumper X22200513 grey remove protection against brush contact from bottom side 12 5 x n 3 length of busbars 0 5 e g 12 5 x 5 3 59 5 0 5 insert protection against brush contact continuous busbar 50...

Page 6: ...MENT ESX10 TA TB ISA 12 12 01 2015 UL File E320024 Operating Temperature Code T4 This equipment is suitable for use in Class Division 2 Groups A B C and D or non hazardous locations only T4 A 0 C to 5...

Page 7: ...7...

Page 8: ...nly In the interest of improved design performance and cost effectiveness the right to make changes in these specifications without notice is reserved Product markings may not be exactly as the orderi...

Reviews: