8
3.3.1 Terminals for voltage supply
Supply XD1
Voltage ratings: DC 24 V(± 5 % → 18 ... 30 V)
Rated current: typically 75 mA
Terminal design: 3 x push-in terminals (+/0V/ FE)
Max. cable cross section rigid
0.2 – 1.5 mm
2
flexible with wire end ferrule (without plastic sleeve) 0.2 – 1.5 mm
2
flexible with wire end ferrule (with plastic sleeve)
0.2 – 0.75 mm
2
cable cross section
AWG24 – AWG16 str.
stripping length
8 mm
Using a supply voltage outside the indicated operating range can cause malfunctions or destruction of the device.
The voltage supply of the CPC12 bus controller is guaranteed via the supply module and the related connector arm.
The use of the line terminals is optional.
3.3.2 PROFINET interfaces with integral switch, connection sleeve XF1, XF2
XF1
Connection to bus system PROFINET
Type: RJ45
When wiring and connecting to the bus system PROFINET the installation and wiring regulations of the PROFIBUS User Organisation
(PNO) have to be observed.
XF2
Connection to bus system PROFINET
Type: RJ45
When wiring and connecting to the bus system PROFINET the installation and wiring regulations of the PROFIBUS User Organisation
(PNO) have to be observed.
3.3.3 ETHERNET interface, connection sleeve X1
X1
Connection with the bus controller CPC12 and the integral web server
Type: RJ45