17
User Manual EE741 Inline Flow Sensor for Compressed Air and Gases
5.2.2 Modbus RTU
EE741 flow sensor can be operated in a Modbus RTU network with max. 32 devices. Writing 0
into the corresponding register will reset the MIN/MAX values and the consumption meter.
For Modbus protocol settings see Application Note Modbus AN0103 (www.epluse.com/EE741).
Modbus Map:
Register number
1)
[DEC]
Register address
2)
[HEX]
Measured value
Unit
Type
Read registers (function code 0x03 / 0x04)
30501
1F4
Temperature
°C
32-bit float
30503
1F6
Temperature
°F
32-bit float
30507
1FA
Standard flow
Nm/s
32-bit float
30509
1FC
Standard flow
SFPM
32-bit float
30511
1FE
Mass flow
kg/h
32-bit float
30513
200
Mass flow
kg/min
32-bit float
30517
204
Standard volume flow
Nm³/h
32-bit float
30519
206
Standard volume flow
Nm³/min
32-bit float
30521
208
Standard volume flow
l/min
32-bit float
30523
20A
Standard volume flow
l/s
32-bit float
30525
20C
Standard volume flow
SCFM
32-bit float
30529
210
Consumption meter status
m³
64-bit-double
30533
214
Consumption meter status
ft³
64-bit-double
31001
3E8
MIN value temperature
°C
32-bit float
31003
3EA
MIN value temperature
°F
32-bit float
31007
3EE
MIN value standard flow
Nm/s
32-bit float
31009
3F0
MIN value standard flow
SFPM
32-bit float
31011
3F2
MIN value mass flow
kg/h
32-bit float
31013
3F4
MIN value mass flow
kg/min
32-bit float
31017
3F8
MIN value standard volume flow
Nm³/h
32-bit float
31019
3FA
MIN value standard volume flow
Nm³/min
32-bit float
31021
3FC
MIN value standard volume flow
l/min
32-bit float
31023
3FE
MIN value standard volume flow
l/s
32-bit float
31025
400
MIN value standard volume flow
SCFM
32-bit float
31501
5DC
MAX value temperature
°C
32-bit float
31503
5DE
MAX value temperature
°F
32-bit float
31507
5E2
MAX value standard flow
Nm/s
32-bit float
31509
5E4
MAX value standard flow
SFPM
32-bit float
31511
5E6
MAX value mass flow
kg/h
32-bit float
31513
5E8
MAX value mass flow
kg/min
32-bit float
31517
5EC
MAX value standard volume flow
Nm³/h
32-bit float
31519
5EE
MAX value standard volume flow
Nm³/min
32-bit float
31521
5F0
MAX value standard volume flow
l/min
32-bit float
31523
5F2
MAX value standard volume flow
l/s
32-bit float
31525
5F4
MAX value standard volume flow
SCFM
32-bit float
Write registers (function code 0x06)
60001
0
Reset MIN value temperature
16-bit integer
60002
1
Reset MIN value standard flow
16-bit integer
60003
2
Reset MIN value mass flow
16-bit integer
60004
3
Reset MIN value standard volume flow
16-bit integer
60005
4
Reset MAX value temperature
16-bit integer
60006
5
Reset MAX value standard flow
16-bit integer
60007
6
Reset MAX value mass flow
16-bit integer
60008
7
Reset MAX value standard volume flow
16-bit integer
60009
8
Reset consumption meter
16-bit integer
1) Register number starts from 1
2) Register address starts from 0
Modbus setup:
Factory settings
Adjustable values
Baud rate
9600
9600, 19200, 38400
Data bits
8
8
Parity
EVEN
None, odd, even
Stop bits
1
1 or 2
Slave address
240
1...247