Operating manual EE23 humidity / temperature sensor
9 Technical Data
Measurands
Relative Humidity
Working range
0...100% RH
Accuracy
1
(including hysteresis, non-linearity and repeatability,
traceable to intern. standards, administrated by NIST, PTB, BEV...
)
EE23-T1/T2/T4/T5 EE23-T6
-15...40°C
(5...104°F)
≤
90% RH
± (1.3 + 0.3%*mv) % RH
± (1.8 + 0,3%*mv) % RH
-15...40°C
(5...104°F)
>90% RH
± 2.3% RH
± 2.8% RH
-25...70°C
(-13...158°F)
± (1.4 + 1%*mv) % RH
± (1.9 + 1%*mv) % RH
-40...180°C
(-40...356°F)
± (1.5 + 1.5%*mv) % RH
-
Temperature dependence electronics
typ. ± 0.015% RH/°C
Response time t
90
with metal grid filter at 20 °C
(68 °F)
< 15 sec.
Temperature
Probe working range
EE23-T1
-40...60°C
(-40...140°F)
EE23-T2/T6
-40...80°C
(-40...176°F)
EE23-T4
-40...120°C
(-40...248°F)
EE23-T5
-40...180°C
(-40...356°F)
Accuracy
Temperature dependence of electronics
typ. 0.002°C/°C
Output Scale Span
from
up to
units
EE23-T1
EE23-T2/T6
EE23-T4
EE23-T5
Humidity
RH
0
100
100
100
100
% RH
Temperature
T
-40
(
-40)
60
(
140)
80
(176)
120
(248)
180
(356)
°C
(°F)
Dew point temperature
Td
-40
(
-40)
60
(140)
80
(176)
100
(212)
100
(212)
°C
(°F)
Frost point temperature
Tf
-40
(
-40)
0
(32)
0
(32)
0
(32)
0
(32)
°C
(°F)
Outputs
0 - 1 V
-0.5 mA < I
L
< 0.5 mA
0 - 5 / 0 - 10 V
-1 mA < I
L
< 1 mA
0 - 20mA / 4 - 20 mA
R
L
< 470 Ohm
General
Supply voltage
for 0 -1 V / 0 - 5 V outputs
10.5 - 35V DC
or
12 - 28V AC
for 0 - 10 V /
0 - 20 mA / 4-20 mA
outputs
15.0 - 35V DC or 15 - 28V AC
100...240V AC, 50/60Hz supply module (optional)
Current consumption for voltage output
for DC supply
≤
25 mA
(with alarm module
≤
35 mA)
for AC supply
≤
45 mA
eff
(with alarm module
≤
70 mA
eff
)
Current consumption for current output
for DC supply
≤
55 mA
(with alarm module
≤
65 mA)
for AC supply
≤
100 mA
eff
(with alarm module
≤
120 mA
eff
)
Enclosure / protection class
PC or Al Si 9 Cu 3 / IP65; NEMA 4
Cable gland
M16x1.5 cable Ø 4.5 - 10 mm (0.18 - 0.39”)
Electrical connection
screw terminals max. 1.5 mm² (AWG 16)
Working temperature range of electronics
-40...60°C
(-40...140°F)
Working temperature range with display
-30...60°C
(-22...140°F)
Storage temperature range
-40...60°C
(-40...140°F)
CE compatibility according
EN61326-1 EN61326-2-3 ICES-003 ClassB
Industrial Environment FCC Part15 ClassB
Alarm Module
2)
Output
SPDT-Switch max. 250V AC/8A or 28V DC/8A
threshold hysteresis
Setting range
10...95% RH
3...15% RH
Setting accuracy
± 3% RH
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in
accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) only for models T1, T2, T4 and T6.
EE23-T1/T2/T4/T5
EE23-T6
°C
°C
∆°
C
∆°
C