INSTALLATION INSTRUCTIONS
E-TFP LED Flat Panel
www.e-conolight.com | 888.243.9445 | FAX: 262.504.5409
CAUTION:
Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
FCC NOTICE Class A
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1.
Connect supply ground to fixture ground (green) lead.
2.
Connect supply common to fixture neutral (AC-N)
terminal on terminal block in driver wiring chamber.
3.
Connect supply Vin to fixture hot (AC-L) terminal on
terminal block in driver wiring chamber.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1.
Connect supply ground to fixture ground (green) lead.
2.
Connect supply L1 (Hot) to fixture neutral (AC-N)
terminal on terminal block in driver wiring chamber.
3.
Connect supply L2 (Hot) to fixture hot (AC-L) terminal
on terminal block in driver wiring chamber.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
DIMMING
1.
If 0-10V dimming is used, connect supply positive
dimming lead to fixture positive dimming
[0-10V (DIM +)] terminal on terminal block in driver
wiring chamber.
2.
If 0-10V dimming is used, connect supply negative
dimming lead to fixture negative dimming
[0-10V (DIM -)] terminal on terminal block in driver
wiring chamber.
FIXTURE WIRING