Figure 6. Distances for Flue Outlets
PLACEMENT
Distance (cm)
PLACEMENT
Distance (cm)
A- Under a window
G- Side of a horz. or vert. pipe
H- Dist. from an outer corne
I- Dist. from an inner corner
L- From floor or pavement
M- Vert. distance between
two flue outlets
N-Horz. distance between
two flue outlets
B- Under an air vent
C- Under rain shield
D- Under a balcony
E- Side of a window
F- Side of an air vent
60
60
30
30
40
60
60
60
100
180
150
100
Flue Connections
E.C.A. Felis boilers are designed to work with C-type flues to provide the air required for burning
from out of boiler room. During flue connections, tightness gaskets should be mounted correctly
to prevent flue gas leakage to the fresh air intake. Horizontal flue kit must be installed with a 3%
slope towards the appliance to keep the condansate water flowing. Different connection kits for
the air intake and flue outlet are provided seperately.
You can use the Felis condensing boiler as a B-type device with a flue adapter that you can
supply from your seller. If the appliance is used as a B-type device, the boiler room must be
equipped with proper ventilation ducts per required by the directives. Felis boiler shall not be
used as a B-type device in environments that the air is polluted with halogenic hydrocarbons
(hair salon, printing press, chemical cleaner shop etc.) That way the appliance can be protected
from the corrosive effects of the ambient air.
Summary of Contents for FELIS FL 100 HM
Page 1: ...FELIS WALL HUNG CONDENSING BOILER FELIS FL 50 65 100 125 150 HM INSTALLATION AND USER MANUAL ...
Page 2: ......
Page 10: ...7 Felis 65 Figure 2b Felis 65 Detailed Drawings ...
Page 11: ...8 Felis 100 125 150 Figure 2c Felis 100 125 150 Detailed Drawings ...
Page 13: ...Figure 3 Electronic Board Circuit Diagram 10 Electrical Board Circuit Diagram ...
Page 18: ... d d l Figure 7 Flue Types 15 I I I I ...
Page 30: ...27 ...
Page 31: ...28 ...
Page 32: ...29 ...
Page 33: ...30 ...
Page 40: ......
Page 46: ......