Information Number
Description
i00
Instant cent
ral heating inlet temperature (°C)
i01
Instant central heating return temperature (°C)
i02
Instant domestic water temperature
(Instantaneous/Tank/Above tank) (°C)
i03
Instant domestic water temperature (Below tank) (°C)
i04
Solar panel
temperature (°C)
i05
Instant flow (L/minute x 10)
i06
Instant outdoor air temperature (°C)
i07
Calculated central heating set temperature (°C)
i08
Number of active relays
i09
Software version
1.3.3. Error History Menu
After pressing and holding K1 for 5 seconds, proceed with K5 and K6 to display "Hi" symbol on the
screen. When you see this symbol, you can enter the error history menu by pressing K1 again. After
entering the menu, you can display the last 8 codes by switching between the last error codes with
K3 and K4. Pressing K1 once while the error codes are displayed on the screen directs to the
service menu selection screen. You can return to the main screen by pressing and holding K1 for 5
seconds. If no button is pressed for 60 seconds, the normal operation screen will be returned.
1.3.4. Annual Maintenance Counter Reset
While the "tS" symbol is displayed on the screen, the password selection menu is accessed by
pressing K1. Here, the value of "11" is reached by using K3 and K4 and the value is selected with K1
or K3. The value "P34" will blink on the screen. K4 allows you to enter and "rE" symbol is displayed
on the screen. The annual maintenance counter is reset by pressing K1 while the "rE" symbol is
displayed on the screen.
1.3.6- Full Capacity Test Mode
Тоа е режимот што му овозможува на уредот да работи со полн капацитет и да контролира
дали се активирани сите отпори. Може да се работи најмногу 3 пати откако уредот ќе се
вклучи. Буквите „Ft“ се појавуваат за време на овој режим на тестирање.
1.3.5- Single Resistor Test Mode
Test mode is activated by pressing K3 and K4 buttons together for 5 seconds. Test mode
simulates a CH heat demand and it activates a single resistor.
Test mode is terminated if K1 button is pressed or Test mode timeout period exceeds.
K4 button -> Changes active relay (Resistor 1 through resistance 9)
K3 button -> Changes active relay (Resistor 9 through resistance 1)
Timeout period is 15 minutes for test mode.
8