P24
Pump overrun time after central heating request (sec)
0-99
60
60
60
60
60
P30
K factor for outdoor temperature sensor compensation
0-30
0
0
0
0
0
P33
Domestic water shut off temperature configuration
0: Stop at 71°C
1: Domestic water set value + FP04
0-1
1
1
1
1
-
F22
Boiler Capacity
6 = 6KW
9=9KW
12 = 12KW
15 = 15KW
18 = 18KW
24 = 24KW
27 = 27KW
6,9,12,15,
18,24,27
24
24
24
24
24
1.3.2. Information Menu
After pressing and holding K1 for 5 seconds, proceed with K5 and K6 to display "In" symbol on the
screen. When you see this symbol, you can enter the information menu by pressing K1 again. After
entering the menu, you can navigate between the information numbers with K5 and K6 and display
the value in the information number you want by pressing K3 or K4 once. While displaying the value
in the information menu, you can change to the information number by pressing K1 once. Pressing
K1 once while on the information number selection screen provides access to the service menu
selection screen. If no button is pressed for 60 seconds, the normal operation screen will be
returned.
The information menu is where you can access some of the instant measurement and operating
information of the device. The values you can access from the information menu are included in the
following table: