7
MAINTENANCE
7.1 MAINTENANCE
Mounting and electrical connection of the SPX must be done by specialists with EMC training, following
all applicable regulations, and in
pressureless, voltage-free, intrinsically safe condition with the
machine switched off.
The machine must be secured against being switched back on!
Burn Hazard!
The SPX can be very hot when removed. WEAR PROTECTIVE GLOVES!
Installation and Removal Instructions
•
DO NOT REMOVE PROTECTIVE CAP UNTIL READY TO INSTALL.
•
PRIOR TO INITIAL INSTALLATION, VERIFY CORRECT MACHINING OF MOUNTING HOLE.
•
WHEN REINSTALLING, MAKE SURE THE PROCESS CONNECTION IS CLEAR OF DEBRIS.
•
ALWAYS REMOVE THE SPX BEFORE CLEANING THE MACHINE WITH ABRASIVES OR STEEL WIRE
BRUSHES, ETC.
•
DO NOT CLEAN THE “SCREWED-IN” SECTION OF THE SPX WITH HARD OBJECTS – THIS WILL
DAMAGE THE SPX.
•
ALWAYS USE A TORQUE WRENCH APPLIED TO THE DESIGNATED WRENCH FLATS. DO NOT
APPLY THE TOOL TO THE HOUSING OR HOUSING/ SENSOR CONNECTION.
•
ELECTROSTATIC DISCHARGE MAY DAMAGE THE SPX – TAKE ESD PRECAUTIONS.
7.2 REPAIR/DISPOSAL
For SPX repair and disposal please contact customer service from our website:
www.dynisco.com/contact
7.3 WARRANTY
The SPX Series Dynisco Pressure transmitters will provide excellent service and superior performance if
proper care is taken during handling, installation, and use. This DYNISCO product is warranted under
terms and conditions set forth in the
DYNISCO
web pages. Go to
www.dynisco.com
and click on the
"warranty" link under the “Post-Sales Support” tab at the top of the web page for complete details.
8 TROUBLESHOOTING
Symptom
Corrective Actions
Milliamp Reading is Zero
1) Check if Power Polarity is Reversed
2) Verify Voltage Across Transmitter Pins