PowerDepot H5B series User Manual
14
3.2.3 Electrical installation
Statement
:
For Australian market, installations should be conducted in accordance with
AS/NZS 3000 and AS/NZS 5139”.
Use multimeter to measure the device before power cable connection procedure. Check
the cable continuity, confirm positive and negative and mark the cable labels.
Measuring methods
:
Power cable check: select the buzzer mode of multimeter and detect the both ends
of the same color cable. If the buzzer calls, it means the cable is in good condition.
After visual testing of power line connection, the positive and negative poles of the
battery shall be connected respectively to the positive and negative poles of
another device (inverter).
Connect the battery box to the ground cable
Customer needs to prepare a M6 OT terminals and ground cables. Connect the battery
shell as shown below. The sectional area of the grounding cable shall be at least 6mm
²
and the bolt locking torque is 6NM.
Grounding
point
Grounding
cable
6. Carry the battery box to the installed
Battery bottom bracket.
Use M6 bolts to connect the Support
bracket&bottom bracket with the box
and control the torque force 6NM.