Operating & Installation Manual for the GSC300 Engine Controller
13
CONTROLLER OVERVIEW
The GSC300 Features the Following Functions:
1.
Controller Programming Adjustability
2.
General Fault Conditions
3.
Not In Auto
4.
Low Battery Voltage Alarm
5.
Oil Pressure Input
6.
Coolant Temperature Input
7.
Fuel Level/Auxiliary Input
8.
Speed Signal Sensing
9.
Adjustable Input Programming
10.
Magnetic Pick-Up Capability Option
1: CONTROLLER PROGRAMMING ADJUSTABILITY:
Adjustable Parameter Ranges:
Crank Disconnect:
12 to 140Hz (Generator Output Version)
44 to 300Hz (Magnetic Pick-up Version)
Overspeed:
60 - 4156Hz (Generator Output Version)
-OR DISABLED BY PC INTERFACE
300 - 8492Hz (Magnetic Pick-up Version)
-OR
DISABLED BY PC INTERFACE
Crank Tries:
1 to 10
Crank/Rest:
3 to 32 seconds
NOTE:
If the engine speed seen by the controller does not go to zero during Crank Rest, the controller will
wait until the speed goes to zero before re-initiating the cranking sequence.
2: GENERAL FAULT CONDITIONS:
The following scenarios can cause the unit to enter the
general fault condition:
Low Fuel/Auxiliary Failure (“XTR_FAIL”)
Low Oil
High Coolant Temperature
Overcrank
Overspeed
Loss of Speed (“SPDLOSS”)
The General Fault output is rated 300mA Max.