SPECIFICATIONS FOR THE GSC300
Operating Voltage:
7 to 30VDC
continuous
,
with zero volts
cranking dropout protection
Operating Temperature:
-40 to +85ºC
Physical Dimensions:
4.5"(H) x 5.5"(W) x 1.25"(D)
Actual Unit Weight:
0.458 lbs
Enclosure:
High Impact Resistant, Injection Molded Plastic Enclosure
Front Panel Indications
-
High intensity LED’s with regulated brightness
LCD Display:
-
Ultra-bright, Backlight LCD display with optimum viewing angle of 0 to -25º from perpendicular
-Display Size (mm): 8 (W) x 32 (H) x 12.8 (D) x 16 characters
Adjustments
Warm-up:
0 - 200 seconds (After Oil Bypass Feature)
Cool-Down:
0 - 255 seconds
Crank Disconnect:
12 to 140Hz (Generator Output Version)
44 to 300Hz (Magnetic Pick-up Version)
Overspeed:
60 - 4156Hz (Generator Output Version)
300 - 8492Hz (Magnetic Pick-up Version)
Crank Rest:
3 - 32 seconds
Delay on Start:
0 – 59 seconds
Crank Tries:
1 to 10
Oil Bypass:
15 – 55 seconds
Low Battery Indication: