AC supply 

The power supply has 3 terminal blocks for Live, Earth and Neutral connections, and is 
protected by a 20mm anti-surge fuse.  Mains earth is isolated from the 0V output, although, 
when supplied boxed, mains earth is connected to the metal enclosure. 

Tamper output 

This output is connected to the tamper connector.  These terminals will be shorted when 
the tamper switch is fitted and closed. 

Fault outputs 

Three voltage free fault outputs and LEDs are provided with the following functions: 

EPS FAULT 

APS FAULT 

PSU FAULT 

Green LED goes out and 
relay contacts open if: 

Green LED goes out and 
relay contacts open if: 

Green LED goes out and  

AC power fault 

PSU over-voltage fault 

Thermal shutdown 

Total power-down 

Battery not connected 

Battery load  test fault 

Battery voltage low 

Total power-down 

Output voltage low 

Total power-down 

All outputs open and LEDs out indicates a total power-down 

 

Status LED 

Status LED 

Indicates 

OFF Normal 
Fast flash 

Learning battery configuration 

Slow flash 

Batteries are charging 

One blink 

Fault on battery connected to BATT1 

Two blinks 

Fault on battery connected to BATT2 

Three blinks 

Fault on battery connected to BATT3 (

D1532 only

 

D1530 Series Installation Manual - D1530-INST/13A/v3                                                                                                          - 

2

 

 

Summary of Contents for D1531

Page 1: ...e EPS OK LED is on If not all the batteries are to be fitted the Status LED will blink Press the Learn button and the Status LED will flash quickly while the battery configuration is learned in The Status LED will start to flash slowly indicating that the batteries are charging If the APS OK LED is off the battery voltage may be low Wait for a couple of minutes to confirm that the APS OK LED comes...

Page 2: ...AULT PSU FAULT Green LED goes out and relay contacts open if Green LED goes out and relay contacts open if Green LED goes out and AC power fault PSU over voltage fault Thermal shutdown Total power down Battery not connected Battery load test fault Battery voltage low Total power down Output voltage low Total power down All outputs open and LEDs out indicates a total power down Status LED Status LE...

Page 3: ...n after a complete power down Battery protection The batteries and electronic circuitry are protected against reverse polarity connected by a self resetting electronic fuse The batteries are also protected against deep discharge which will be invoked when the battery terminal voltage has dropped to 10 5v Battery monitoring The batteries are monitored for low voltage disconnection and load test Whe...

Page 4: ...e table below To meet the requirements of EN50131 1 the figures below must be divided by 2 2 e g 1 5A becomes 0 68A D1531 D1532 D1531 D1532 1 x 7 AH 0 5A 0 5A 1 x 8 AH 0 6A 0 6A 2 x 7 AH 1 0A 1 0A 2 x 8 AH 1 0A 1 2A 3 x 7 AH N A 1 5A 3 x 8 AH N A 1 8A 1 x 17 AH N A 1 3A 1 x 18 AH N A 1 4A 2 x 17 AH N A 2 0A 2 x 18 AH N A 2 0A Note in both the above tables it is assumed that the system transmits a ...

Reviews: