Dwyer Instruments RTI2 Series Instructions Manual Download Page 11

Page 10

RTI2 INSTRUCTIONS

Dwyer Instruments, Inc. • 219.879.8868 • www.dwyer-inst.com 

InP

 

View or change the filter (set F), jitter (set J), enable 

reed mode. Use the filter setting if the display is jumping 

excessively due to flow conditions. Use the jitter setting to 

enter a time delay to handle start up conditions. Jitter units 

are seconds.

Protected Features

To enter the protected features use the left/right arrow 

keys to navigate to the Pcode tab, found in the secondary 

menu. Press the enter key and then enter the passcode. The 

protected menu, shown below, will now be displayed. The 

tabs have the following functions:

Set CD

  Enter a user created numerical passcode.

Lock

  Lock menu functions to prevent unauthorized 

 

changes.

E/D R

  Disable or enable the total volume reset function.

PCNT

  Keeps a running tally of the number of times the 

 

passcode has been used.

OutP

 

Enters the menu where the default output functions are 

selected.

The P/A tab changes the function of the outputs. Default 

is scaled pulse out for both outputs. Either output can be 

changed to alarm high or alarm low. If alarm options are 

selected menu tabs for setting the alarms will be displayed 

on the main menu (alarm 1) or the secondary menu (alarm 

2) If the alarm options are selected a Set H (hysteresis) tab 

is available. The hysteresis entry is a % value. The value 

defines the % change required  for a change in alarm state to 

occur.

The factory setting will show Set P2 which allows one to 

view or change the volume of flow totalized per pulse sent to 

pulse out 2. The units for Set P2 follow the units selected for 

the rate display. If P2 is selected as an alarm the menus will 

change to Set A2 and a Set H (hysteresis) tab is available. 

The hysteresis entry is a % value. The value defines the % 

change required for a change in alarm state to occur.

Set 4 input the flow rate at which 4 mA (min) output is de

-

sired.

ADJ L allows the adjustment of the 4 mA and 20 mA values 

so that one can tune performance of the RTI2 to match the 

installed system values. The adjustment units range for 

0-32? Positive values adjust the setting incrementally larger 

and negative values adjust the setting incrementally lower.

The RTI2 Secondary Menu Functions

SETTINGS

Summary of Contents for RTI2 Series

Page 1: ...31 F 0 to 55 C Storage 40 to 158 F 40 to 75 C Output Current sinking square wave pulse Scaled pulse output 0 1 s duration 6 1 Hz max or high alarm output or low alarm output sensor pass through pulse...

Page 2: ...Optional Protective Cover Closed PROUDLY MADE IN THE USA RTI2 Series RATE TOTAL INDICATOR INSTRUCTIONS RTI2 SERIES RATE TOTAL INDICATOR INSTRUCTIONS...

Page 3: ...eter Page 7 RTI2 139 EX Magmeter Page 7 Settings K Factor Changing Flow Indicator Settings Page 8 RTI2 Secondary Menu Functions Page 10 Troubleshooting Problems Probable Causes Things to Try Page 11 T...

Page 4: ...for the RTI2 with dual 24 and 12VDC outputs to power both the loop and sensors requiring more power than the loop can supply Pulse and 4 20mA analog outputs can be used to signal external devices e g...

Page 5: ...when loop powered Display Rate 5 digit autorange Total 8 digit Units Rate Units Gallons Second Minute Hour Day Liter Second Minute Hour Day Cubic Feet Second Minute Hour Day Cubic Meters Second Minute...

Page 6: ...nverted from a wall mount to a meter mount using the mounting kit contact distributor that includes a lower housing and associated hardware and installs as follows 1 Remove the strain relief through w...

Page 7: ..._ _ S PULSE OUT 2 PULSE OUT 1 _ _ FT440 GREEN WHITE BLACK _ FT440 139 Dual Power Supply Lower Housing 4 20mA Device _ Dashed line shows terminal connection if 4 20mA device is not used To 115Vac Power...

Page 8: ...0Vdc 12 24Vdc 12 Vdc Power Supply _ _ _ _ S White Green Red Black Red 4 20mA Device _ 9 30 Vdc Power Supply _ Red Black _ S _ RTI2 Zero Adj Status LED 1 Option Only 2 3 4 5 6 Reverse Output Forward Ou...

Page 9: ...ALLON OF FLOW All menu screens consist of two rows of tabs surrounding a dialog box that lets you view and change setup parameters Set K R UNIT SET K T UNIT SET D SET P RESET EXIT 086238 235 PRESS TO...

Page 10: ...total flow volume to zero This tab is not available when the 64 non resettable total option is ordered Exit R UNIT SET K T UNIT SET D SET P RESET EXIT PRESS TO EXIT MENU AND RETURN TO FLOW DISPLAY Re...

Page 11: ...for both outputs Either output can be changed to alarm high or alarm low If alarm options are selected menu tabs for setting the alarms will be displayed on the main menu alarm 1 or the secondary menu...

Page 12: ...or incorrect 4 20mA output RTI2 only Wrong 4mA setting or wrong 20mA setting Use Set 4 to correct target minimum flow rate Use Set 20 to correct target top flow rate Inadequate loop power supply volt...

Page 13: ...LT 14301r1 1 20160301 3 1 16 Dwyer Instruments Inc 102 Indiana Highway 212 Michigan City IN 46360 USA P 219 879 8868 F 219 872 9057 1 800 872 9141 www dwyer inst com...